Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
3 Product description
83054802 1/2018-07 La
41-228
3.4.10 Analogue output
FE
1
2
X63
3
0
4-20 mA
If the combustion manager is equipped with an internal load controller, a system
value can be issued at output X63 via an analogue signal (0/4 … 20 mA). The out-
put can be configured in parameter
Analog Output
Load signal
If the parameter
Selection analog output
is set to
Load
the analogue
signal corresponds to defined values. For different scaling, the parameter has to be
set to
Load 0
.
Modulating operation:
Burner capacity
OFF
0 %
100 %
Analogue signal
4 mA
4 mA
20 mA
Multi-stage operation:
Burner capacity
OFF
Stage 1
Stage 2
Stage 3
Analogue signal
4 mA
5 mA
10 mA
15 mA
3.4.11 Frequency converter
FE
1
2
X73
3
4
6
5
Start OUT
0
U1
WH
BN
GN
YE
GY
The frequency converter is connected to output X73 using a screened cable
(W-FM 200 only). The screen must be connected to ground on both sides.
Terminal
(W-FM 200)
Function
X73:1/2
Enable contact:
The enable contact for the frequency converter closes from a de-
sired speed greater than 0 %.
The switch status in phase 10 (home run) for the standby position
(0 %) can be specified via parameter
ReleasecontctVSD
X73:3
Alarm input:
A signal from the frequency converter (DC 12 … 24 V) results in
a safety shutdown.
X73:4/5
Setpoint output (0/4 … 20 mA):
The output and input (W-FM 200 / frequency converter) must be
matched. The output signal can be set in parameter
Setpoint
Output