3 Product description
83054802 1/2018-07 La
12-228
3 Product description
3.1 Variations
Type
Version
Functions
W-FM 100
LMV51.0…
Burner Control
Low gas programme
Valve proving
LMV51.1…
as type LMV51.0…
Load controller
W-FM 200
LMV52.2…
as type LMV51.1…
Variable speed drive
O
2
trim
LMV52.4…
as type LMV52.2…
FGR with temperature compensation
CO monitor and CO controller function
3.2 Function
3.2.1 Burner Control
A burner control for oil, gas and dual fuel burners is integrated in the combustion
manager.
It controls the sequence of operation, monitors the flame and communicates with all
components.
3.2.2 Low gas programme
The low gas pressure switch monitors the gas connection pressure from phase 21.
If the gas pressure set at the low gas pressure switch is not achieved, the combus-
tion manager initiates a safety shutdown and starts the low gas programme.
In the low gas programme, the combustion manager initiates a restart after the low
gas waiting time (Parameter:
DelayLackGas
). This low gas waiting time doubles
after every unsuccessful start attempt. If the start attempts exceed the repetition
limit value (Parameter:
StartRelease
) the combustion manager goes to lockout.
The repetition counter and the low gas waiting time are automatically reset when
the burner starts.