6 Operation
83054802 1/2018-07 La
114-228
6.10.17 O2 setpoint
Param & Display
O2 module
Process Data
O2 Setpoint
or
Operation
O2 module
O2 Setpoint
Parameter
O2 Setpoint
shows the O
2
setpoint set for the current burner capa-
city.
The O
2
setpoints are defined during commissioning.
6.10.18 Combustion air temperature / CO switching threshold
Param & Display
O2 module
Process Data
Supply air temperat-
ure
or
Operation
O2 module
Supply air temperat-
ure
Parameter
Supply air temperature
shows the combustion air temperature
currently measured, if the relevant sensor is connected to the O
2
module.
In conjunction with CO monitoring, the parameter shows the status of the CO
switching threshold [ch. 3.3.24].
6.10.19 Flue gas temperature
Param & Display
O2 module
Process Data
Flue gas temperature
or
Operation
O2 module
Flue gas temperature
If a flue gas temperature sensor is connected to the O
2
module, parameter
Flue
gas temperature
shows the current flue gas temperature [ch. 3.3.23].
6.10.20 O2 sensor temperature
Param & Display
O2 module
Process Data
QGO SensorTemp
Parameter
QGO SensorTemp
shows the current temperature of the O
2
sensor.
The temperature is detected by a thermocouple in the sensor, 700 °C corresponds
to approx. 29.1 mV.
O
2
trim is activated at a sensor temperature of 700 °C (±15 °C). If the operating
temperature is not achieved, the W-FM reacts according to the operating mode set
[ch. 6.10.1].
If the temperature exceeds 750 °C, deactivate the sensor and check the electrical
connection.