![Weishaupt W-FM 100 Скачать руководство пользователя страница 83](http://html.mh-extra.com/html/weishaupt/w-fm-100/w-fm-100_installation-and-operating-instruction_953373083.webp)
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
83-228
6.8.10 Configuring output X4-03
Param & Display
Burner Control
Configuration
Config input/
output
Start/PS valve
Parameter
Start/PS valve
determines if output X4-03 is used for a start sig-
nal or for pressure switch relief [ch. 3.4.4].
Setting
Function
Start signal
Output X4-03:3 is activated in phase 21 to 79.
PS Relief
Output X4-03:3 is activated in phase 79.
Function is not used.
PS Reli_Inv
In phase 21 and phase 79 the relief valve at out-
put X4-03:3 is de-energised and the air pressure switch
is tested.
6.8.11 Extraneous light
Param & Display
Burner Control
Configuration
ConfigFlameDet
ReacExtranLight
Parameter
ReacExtranLight
determines the reaction if extraneous light is
present in Standby (Phase 12).
Setting
Function
Lockout
Flame signal in phase 12 triggers a lockout.
Startblock
A flame signal in phase 12 leads to start prevention.
6.8.12 Repetition counter
Param & Display
Burner Control
Configuration
RepetitCounter
The parameters in menu
RepetitCounter
determine the number of safety
shutdowns until shutdown with lockout is initiated. Changes in the repetition
counter are only adapted after a reset or if the voltage supply has been interrupted.
Parameters
Function
LossOfFlame
Number of safety shutdowns due to missing flame signal.
Range: (1 …
2
)
HeavyOil
Number of safety shutdowns caused by return temperat-
ure sensor for nozzle circulation not being released
[ch. 3.3.10].
Range: (1 …
3
… 16
(1
)
StartRelease
Number of start preventions with display messages nozzle
circulation [ch. 3.3.10].
Range: (1 …
10
… 16
(1
)
SafetyLoop
Number of safety shutdowns caused by the safety circuit
not being released [ch. 3.3.2].
Range: (1 …
16
(1
)
(1
Repetition value 16 means not limited, no shutdown with lockout is initiated.