7 Commissioning
83054802 1/2018-07 La
181-228
5. Set setpoint step
For modulating operation:
Select
StageSetp_Mod
.
Set setpoint step using the dial knob and confirm with [Enter].
Use [esc] to return to the display
StageSetp_Mod
.
For multi-stage operation:
Select
StageSetp_Stage
.
Set setpoint step using the dial knob and confirm with [Enter].
Use [esc] to return to the display
StageSetp_Stage
.
6. Set residence time
For modulating operation:
Select
MaxTmeMod
.
Set setpoint step using the dial knob and confirm with [Enter].
Use [esc] to return to the display
MaxTmeMod
.
For multi-stage operation:
Select
MaxTmeStage
.
Set setpoint step using the dial knob and confirm with [Enter].
Use [esc] to return to the display
MaxTmeStage
.
7. Carry out data backup
Exit level using the [esc] key.
The display shows
Create parameter backup?
.
Start data backup by pressing [ENTER] key.
The display shows
Parameters are being updated
and the
Para-
meters have been saved
.
The values have been backed up from the combustion manager to the ABE.
Exit level using the [esc] key.