Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
7 Commissioning
83054802 1/2018-07 La
171-228
13. Set burner to automatic operation
Exit level using the [esc] key.
Select
Autom/Manual/Off
.
Set
Automatic
.
Exit level using the [esc] key.
If necessary set load controller and O
2
trim.
14. Carry out data backup
Exit level using the [esc] key.
The display shows
Create parameter backup?
.
Start data backup by pressing [ENTER] key.
The display shows
Parameters are being updated
and the
Para-
meters have been saved
.
The values have been backed up from the combustion manager to the ABE.
Exit level using the [esc] key.