Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
101-228
Direct entry:
Select
O2 MinValue
and confirm with [ENTER].
Change values using the dial knob and confirm with [ENTER].
Exit entry using [esc].
Point: 9 100%
O2 MinValue : 0.7
P-Air manual:
Point: 9 100%
O2 MinValue :XXXX
P-Air manual:
Point: 9 100%
O2 MinValue :XXXX
P-Air manual: 0.0
Point: 9 100%
O2 MinValue : 0.7
P-Air manual: 0.0
Point: 9 100%
O2 MinValue : 0.7
P-Air manual: 0.0
Determine O
2
min value:
Select parameter
P-Air Manual
and confirm with [Enter].
The display shows the current O
2
actual value and the burner drives to the load
point.
Reduce air rating using the dial knob until the combustion limit is reached
(CO content approx. 100 ppm or smoke number approx. 1).
Press [ENTER] to accept the O
2
actual value.
The display shows the value determined as
O2 MinValue
.
Exit entry using [esc].
Point: 9 100%
O2 MinValue : 0.7
P-Air manual:
Point: 9 100%
O2 MinValue :XXXX
P-Air manual:
Point: 9 100%
O2 MinValue : 3.8
P-Air manual: 0.0
Point: 9 100%
O2 MinValue : 0.7
P-Air manual:10.4
Point: 9 100%
O2 MinValue : 0.7
P-Air manual:10.4
O
2
-maximum monitor
Parameter
O2 MaxValue
determines the upper limit value for the O
2
monitor.
The limit value is valid across the entire load range. If the O
2
content in the flue gas
exceeds this limit value for more than 3 seconds, the W-FM reacts in accordance
with the operating mode set [ch. 6.10.1].
Repetition for O
2
minimum monitor
Parameter
NumMinUntilDeact
determines the number of repetitions until the
O
2
controller is deactivated. The parameter is only relevant, if the operating mode is
set to
conAutoDeac
If a rapid load change triggers the O
2
minimum monitor, increase parameter
O2-
ModOffset