6 Operation
83054802 1/2018-07 La
123-228
6.12.4 Analogue inputs
Input X61
Param & Display
LoadController
Configuration
Ext Inp X61 U/I
If a sensor is connected to input X61, the input has to be matched to the sensor in
parameter
Ext Inp X61 U/I
The voltage supply (20 V DC) on terminal X61:1 can not be changed.
Setting
Function
4..20 mA
Current signal with load monitoring
0..20 mA
Current signal without load monitoring
2..10 V
Voltage signal with load monitoring
0..10 V
Voltage signal without load monitoring
Input X62
Param & Display
LoadController
Configuration
Ext Inp X62 U/I
or
Param & Display
SystemConfig
Ext Inp X62 U/I
If an analogue setpoint or load signal is present at input X62, the input must be
matched to the analogue signal in parameter
Ext Inp X62 U/I
Setting
Function
4..20 mA
Current signal with load monitoring
0..20 mA
Current signal without load monitoring
2..10 V
Voltage signal with load monitoring
0..10 V
Voltage signal without load monitoring