Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
96-228
6.9.8 Load limit
Operation
User Maxload
User MaxLoadMod
User MaxLoad Stg
Parameters
Function
User MaxLoadMod
Load limit for modulating operation.
Further restricts full load within the load limits [ch. 6.9.7].
User MaxLoadStg
Load limit for multi-stage operation.
The burner drives only to the stage set.
6.9.9 Start point
Param & Display
RatioControl
GasSettings
OilSettings
StartPointOp
Parameter
StartPointOp
determines the load point for partial load position in
phase 54. In phase 54, the burner drives to the load point set, when the load point
is reached, the W-FM changes over to phase 60 and load control is released.