Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
119-228
6.12 Load controller
The W-FM 200 is equipped with an internal PID load controller as standard, with
the W-FM 100 the internal load controller is optional.
6.12.1 Setpoint
Operation
BoilerSetpoint
SetpointW1
SetpointW2
or
Param & Display
LoadController
ControlParam
SetpointW1
SetpointW2
Two setpoints (W1/W2) can be specified for the internal load controller using
parameters
Setpoint …
.
The setpoints can not be set via the temperature monitor
TL_Thresh_Off
[ch. 6.12.13].
A potential free contact at input X62 can be used to switch between the setpoints
W1 and W2 or to switch from an external to the internal setpoint W1 [ch. 3.3.19].