Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
9 Troubleshooting
83054802 1/2018-07 La
206-228
Fault
codes
Diagnostic
code
Cause
Rectification
44
01 … 04
Deactivated input connected.
Activate input or connect nothing.
Some inputs can only be activated in the
OEM level.
01
Load controller input X62
02
Air pressure switch input X3-02
03
Fan contactor contact input X4-01:3
04
Low gas pressure switch input X9-03:4
05
High gas pressure switch input X9-03:3
06
Min. oil pressure switch input X5-01
07
Max. oil pressure switch input X5-02
08
Start release Oil input X6-01:1
09
Heavy oil immediate start input X6-01:3
0A
Start release Gas input X7-03:2
0B
Safety temperature monitor for high temperat-
ure input X6-01:3
45
–
Safety shutdown during safety temperature
limiter test
46
01 … 07
Program stop is activated, the program se-
quence stops in the defined phase
Deactivate the program stop if it is no
longer required [ch. 6.9.4].
01
Stop in phase 24, pre-purge position
02
Stop in phase 32, auxiliary actuator3 in pre-
purge position
03
Stop in phase 36, ignition position
04
Stop in phase 44, flame signal
05
Stop in phase 52, ignition pilot valve OFF
06
Stop in phase 72, post-purge position
07
Stop in phase 76, auxiliary actuator3 in post-
purge position
47
–
Signal start release Gas input X7-03:2 miss-
ing
48
00
2 flame signals instead of one present
49
01
External flame detector connected via contact
and flame sensor
If an external flame detector is connected to
X6-01:3, no flame sensor must be connected
to X10.
02
External flame detector for high temperature
connected via contact and 2 flame sensors
If an external high temperature monitor is con-
nected to X6-01:3, only one flame sensor
may be connected to X10 for low-temperat-
ure operation.
50
00 … 07
Error in key value test
Internal fault
(1
51
00 … 07
Time block overrun
Internal fault
(1
52
00 … 03
Stack fault
Internal fault
(1
53
01
Incorrect reset condition
Internal fault
(1
(1
If occurring sporadically: Optimise EMC measures. If occurring continuously replace defective component.