Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
126-228
6.12.7 Analogue output
Param & Display
LoadController
Configuration
Analog output
or
Param & Display
SystemConfig
LC Analog Output
The analogue output X63 is configured in menu
Analog Output
Stipulate output value (
OutValuSelection
)
Parameter
OutValuSelection
stipulates the value that is output as a current
signal at output X63
Setting
Function
Load
(1
Load 0
Load signal from internal load controller
O2
Residual oxygen content in flue gas
Pos Air
Pos fuel
Pos Aux…
Position of the relevant actuator
Speed VSD
Setpoint speed
Flame
Flame Signal
Temp Pt…
Temp Ni1000
Temperature sensor input X60
Temp X61
Press X61
Temperature/ pressure sensor input X61
(1
Current range, output value and scaling are predefined and can not be changed
Current range (
CurrMode 0/4mA 0/4mA
)
Parameter
CurrMode 0/4mA
defines the current range at output X63.
0..20mA
4..20mA