7 Commissioning
83054802 1/2018-07 La
187-228
7.5.2 Set CO control
Commissioning of the O
2
controller must be completed for the CO control.
1. Define combustion air sensors
Select
Param & Display
.
Select
O2 Module
.
Select
Configuration
.
Select
SupAirTempSens
.
Select
Pt1000
using dial knob and confirm with [Enter].
Exit display using the [esc] key.
2. Set flue gas temperature warning threshold
Select
MaxTempFlueGas …
.
Set
850
°C using dial knob and confirm with [Enter].
Use [esc] to return to the display
O2 Module
.
On dual fuel burners, set both
MaxTempFlGasGas
and
MaxTempFlGasOil
.
3. Set blocking time
To ensure that an increased CO content during burner start does not initiate a
safety shutdown, the factor for the blocking time must be set to a minimum of 10
[ch. 6.10.5].
Select
O2 Contr/Alarm
.
Select
GasSettings
or
OilSettings
.
Select
NumberTauSuspend
.
Set a minimum of
10
using dial knob and confirm with [Enter].
Use [esc] to return to the display
O2 Module
.
On dual fuel burners repeat procedure.