6 Operation
83054802 1/2018-07 La
124-228
6.12.5 Measuring range
Param & Display
LoadController
Configuration
MeasureRangePtNi
(1
var.RangePtNi
MRange TempSensor
MRange PressSens
(1
Parameter
MeasureRangePtNi
can also be called up via
Param & Display / System config. /
Temp.Limiter
.
The measuring range of the actual value sensor is specified in the parameters.
Temperature sensor (input X60)
The measuring range starts at 0 °C (32 °F) and can not be altered.
The values are available in parameter
MeasureRangePtNi
for the end of the
measuring range:
150°C/302°F
400°C/752°F
850°C/1562°F
(factory setting)
Parameter
var.RangePtNi
can be used to restrict the end of the measuring
range as required. Prerequisite is that the value in parameter
Meas-
ureRangePtNi
is set to
850°C/1562°F
. The scaling of the resistance curve
does not change.
Values approx. 10 % above the end of measuring range are interpreted as sensor
short circuit.
Only required in conjunction with flue gas recirculation
If the sensor is used as FGR temperature sensor, parameter
Meas-
ureRangePtNi
must be set to
850°C/1562°F
and in parameter
var.RangePtNi
the maximum permissible FGR temperature must be set.
Sensor (input X61)
The measuring range starts at 0 °C (32 °F) or 0 bar (0 psi) and can not be altered.
The end of the measuring range can be set in the relevant parameter.
MRange TempSens
: max 2000 °C (3632 °F)
MRange PressSens
: max 100 bar (1450 psi)
Values 10 % outside of the measuring range are interpreted as sensor short circuit
or line break.