6 Operation
83054802 1/2018-07 La
94-228
6.9.7 Load range
LoadLimits
Param & Display
RatioControl
GasSettings
OilSettings
LoadLimits
MinLoad_…
MaxLoad_…
In modulating operation, the load limits restrict the load range within the compound
curves programmed. On dual fuel burners, the load limits for each fuel can be set
separately.
Minimum load:
Parameter
MinLoad_…
limits the load range downward (partial load). Minimum
load can not be set below load point 1, in conjunction with O
2
trim not below load
point 2.
Maximum load:
Parameter
MaxLoad_…
limits the load range upwards (full load).
0 %
100 %
P1
1
3
2
1
Minimum load
MinLoad_…
2
Maximum load
MaxLoad_…
3
Load range