![Weishaupt W-FM 100 Скачать руководство пользователя страница 173](http://html.mh-extra.com/html/weishaupt/w-fm-100/w-fm-100_installation-and-operating-instruction_953373173.webp)
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
7 Commissioning
83054802 1/2018-07 La
173-228
3. Check mixing pressure in ignition position
Select
SpecialPositions
.
Select
ProgramStop
.
Select
36 IgnPos
.
Use [esc] key to return to the display with
OilSettings
.
Select
Autom/Manual/Off
.
Select
Manual
(Burner On).
The burner starts and stops in ignition position without flame formation
Check rotation direction of fan wheel.
Check mixing pressure in ignition position, see installation and operating manual
of burner.
If necessary, adjust mixing pressure via air damper setting:
Select
OilSettings
Select
SpecialPositions
.
Select
IgnitionPos
.
Select
IgnitionPosGas
and adjust.
Use [esc] key to return to the display
IgnitionPos
.
4. Check pump pressure
The pump pressure must be set according to the nozzle selected.
On light oil burners with magnetic coupling between burner motor and oil pump or
with separate oil pump, the pump pressure can only be set in the next step during
ignition.
Check pump pressure at pressure gauge.
Remove closing cap
1
(types T and TA only).
Undo locknut
2
(types T and TA only).
Set pump pressure using pressure regulating screw
3
.
increase pressure: clockwise rotation,
decrease pressure: anticlockwise rotation.
+
1
3
3
3
2
2
3
1
5. Ignition
Set
Program stop
to
44 Interv 1
.
The burner starts and the stepping motor stops in ignition position.
Check combustion values in ignition position.
Set O
2
content of approx. 5 % via air damper setting (
IgnitionPosAir
) whilst
observing the mixing pressure.