Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
7 Commissioning
83054802 1/2018-07 La
175-228
12. Define switch-off points AS2 and AS3
In menu
CurveSet
select option
Without start
.
Select switch-off point
AS2
.
Set air damper setting in switch-on point
ES2
.
Select switch-off point
AS3
.
Set air damper setting in switch-on point
ES3
.
Use [esc] key to return to the display
CurveSet
.
13. Optimise operating points BS1 and BS2
Once full load has been adjusted and the pump pressure has been set to its final
value, the operating points should be optimised.
In menu
CurveSet
select option
With start
.
Select
BS1
.
Check combustion values and, if necessary, adjust via air damper setting (
Air
).
Select
BS2
and also adjust.
14. Check switch points
Activate operating points several times and observe switch-over behaviour.
If necessary optimise operating behaviour:
Adjust switch-off point in menu
Without start
whilst increasing the air
damper setting to avoid soot and CO formation
Adjust switch-on points in menu
With start
15. Check start behaviour
Switch off and restart burner.
Check start behaviour and if necessary correct ignition position.
If the ignition position has been altered:
Re-check start behaviour.
16. Set burner to automatic operation
Exit level using the [esc] key.
Select
Autom/Manual/Off
.
Set
Automatic
.
Use [esc] key to return to the display with
Param & Display
.
Select
ManualOperation
.
Select
SetLoad
.
Set highest stage as the target load.
Exit level using the [esc] key.
If necessary adjust load controller.
17. Carry out data backup
Exit level using the [esc] key.
The display shows
Create parameter backup?
.
Start data backup by pressing [ENTER] key.
The display shows
Parameters are being updated
and the
Para-
meters have been saved
.
The values have been backed up from the combustion manager to the ABE.
Exit level using the [esc] key.