6.16 Data backup
6.16.1 Backup copy
Updating
Param backup
BackupInfo
LMV5x -> AZL
AZL -> LMV5x
Information for backup
Menu
BackupInfo
displays the date, time and the contents of the last data
backup.
Parameters
Function
Date
Date of the last backup copy.
TimeOfDay
Time of the last backup copy.
BU included?
Indicates whether the information from the W-FM has
been transferred without errors.
AZL included?
Indicates whether a display and operating unit was con-
nected during the last backup.
ACT… included?
Shows the actuators connected during the last data
back-up.
VSD included?
Indicates whether a frequency converter module was
saved in the backup copy.
O2 included?
Indicates whether an O
2
module was saved in the backup
copy.
Creating a backup copy
Parameter
LMV5x -> AZL
creates a backup copy of the W-FM in the display
and operating unit (ABE)
The existing data is overwritten.
The data from the W-FM can be backed up to any ABE.
Select parameter
LMV5x -> AZL
and confirm with [ENTER].
Start process with [Enter].
Exit level using the [esc] key.
Param & Display
Updating
Enter PW
Deactivate PW
Param backup
Load SW from PC
Backup-Info
LMV5x -> AZL
AZL -> LMV5x
LMV5x -> AZL
Start process
with ENTER
Abort with ESC
Parameters being
updated
Abort with ESC
Backup being
created
Parameters were
saved
Continue w ESC
Param backup