CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
100
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Scale of the Analog Output indications:
- Full scale =10V: for Output AO1.
- Full scale =20mA for Output AO2.
Check the available options in Table 6.25.
The states of the digital inputs can be monitored in parameter P012.
“Enable/Disable”
= Closed/Open Digital Input DI1 respectively. No
specific Parameter need to be programmed for this function. Only
programming of the Enable/Disable command for the digital input is
required. .
“Start/Stop”
= When P264=1 (Start/Stop at three wires) is
programmed, the digital input DI1 and DI2 become automatically:
DI1=Start and DI2=Stop. Use pulsing switches.
P264
(1)
0 to 2
Digital Input DI2
[ 2=Error Reset ]
Function
-
P265
(1)
0 to 2
Digital Input DI3
[ 0=Not used ]
Function
-
P266
(1)
0 to 6
Digital Input DI4
[ 0=Not used ]
Function
-
Current (%In of the SSW)
Input Voltage (%Un of the SSW)
Output Voltage (%Un of the SSW)
Power Factor
Motor Thermal Protection
Power (W)
Power (VA)
Torque (% In Motor)
Fieldbus
Serial
P251
P253
Gain
P252, P254
AO1
AO2
Figure 6.15 -
Block diagram of the Analog Outputs
Table 6.24
- Functions of the Analog Outputs
P251/P253 Function of the Analog Output
Full Scale when
0
Not used
-
1
Current in % In of the SSW
5 x P295
2
Input Voltage in %Un of the SSW
1.5 x P296(max.)
3
Motor Voltage in % Un of the SSW 1.5 x P296(max.)
4
Power Factor
P008 = 1.00
5
Thermal Protection
P050 = 250%
6
Power in W
1.5 x
3 x P295 x P296(max.) x P008
7
Power in VA
1.5 x
3 x P295 x P296(max.)
8
Torque in %Tn of the Motor
P009 = 100%
9
Fieldbus
16383 (3FFFh)
10
Serial
16383 (3FFFh)