Current
100% In
(A )
147
225
294
355
441
540
631
713
831
1046
1160
1420
1645
1905
2424
Model
SSW-06.0085
SSW-06.0130
SSW-06.0170
SSW-06.0205
SSW-06.0255
SSW-06.0312
SSW-06.0365
SSW-06.0412
SSW-06.0480
SSW-06.0604
SSW-06.0670
SSW-06.0820
SSW-06.0950
SSW-06.1100
SSW-06.1400
Line
Cables
(mm²)
70
95
150
185
300
400
500
2 x 185
2 x 240
4 x 120
4 x 150
4 x 185
4 x 240
4 x 300
4 x 500
Line
Bus
(mm x mm)
20 x 3
20 x 3
25 x 5
25 x 5
30 x 5
40 x 5
60 x 5
40x10
40x10
50x10
60x10
80x10
100x10
120x10
160x10
Motor
Cables
(mm²)
25
50
70
95
120
185
240
240
300
2 x 150
2 x 185
2 x 240
2 x 300
4 x 150
4 x 185
Motor
Bus
(mm x mm)
12 x 2
20 x 3
20 x 3
20 x 3
25 x 5
25 x 5
25 x 5
30x5
40x5
40x5
40x10
40x10
50x10
60x10
80x10
Grounding
Cables
(mm²)
10
25
35
50
70
95
120
120
150
150
185
240
300
2 x 150
2 x 185
Table 3.7
- Recommended cables for inside delta motor connection
DANGER!
The AC input voltage must be compatible with the Soft-Starter SSW-06
rated voltage.
DANGER!
Provide power supply disconnecting switch. This disconnecting switch
must disconnect the AC input voltage from the Soft-Starter SSW-06,
always when required (for instance during maintenance services).
DANGER!
If a disconnect switch or a contactor is inserted in the motor supply
line, DO NOT operate these devices with running motor or when
Soft-Starter SSW-06 is enabled.
ATTENTION!
Control of overvoltage in the line that supplies the Soft-Starter must be
made using surge protection with a voltage of 680 Vac (phase to phase
connection) and energy absorption capacity of 40 joules (for models
from 85A to 205A) or 80 joules (for models from 255A to 1400A).
NOTE!
Use wire sizing and fuses as recommended in Table 3.6, 3.7 and 3.9.
The connector tightening torque is as indicated in Table 3.5. Use 70ºC
(158ºF) copper wires only.
3.2.4