CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
103
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P295
(1) (2)
0 to 20
Rated Current
[ According to the
rated current of the
Soft-Starter
SSW-06 ]
-
ATTENTION!
Program always this parameter with a voltage that matches
exactly the voltage of the model of your Soft-Starter SSW-06.
P296
(1) (2)
0 or 1
Rated Voltage
[ According to the
rated voltage of the
Soft-Starter
SSW-06 ]
-
Table 6.26 -
Functions of the Relay Outputs
P296
Voltage Range
0
220/575V
1
575/890V
Table 6.28 -
Voltage range
RLx Parameter P277
P278
P279
Function
(RL1)
(RL2)
(RL3)
Not used
0
0
0
In Operation
1
1
1
At full Voltage
2
2
2
External By-pass
3
3
3
FWD/REV-K1
4
-
-
FWD/REV-K2
-
4
-
DC-Braking
5
5
5
No Fault
6
6
6
Fault
7
7
7
Fieldbus
8
8
8
Serial
9
9
9
“No Fault”
= the output is enabled without error. i. and., if the Soft-
Starter SSW-06 is not disabled due to any error.
“Fault”
= the output is enabled with error. i. and., if the Soft-Starter
SSW-06 is disabled due to any error.
ATTENTION!
Always Program this parameter with a current that matches exactly
the current of the model of your Soft-Starter SSW-06. Error in
programming this parameter maydamage your Soft-Starter SSW-06
exactly.
Table 6.27
– Rated current configuration
P295
Rated
Current
P295
Rated
Current
P295
Rated
Current
0
10A
7
130A
14
480A
1
16A
8
170A
15
604A
2
23A
9
205A
16
670A
3
30A
10
255A
17
820A
4
45A
11
312A
18
950A
5
60A
12
365A
19
1100A
6
85A
13
412A
20
1400A