CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
82
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Indication of the state of motor thermal protection in a scale of 0% to
250%. Being 250 the thermal protection functioning point of the mo-
tor, indicating an error.
The value indicated in this parameter depends on the motor working
condition and how long it has been in this condition, for example:
stopped, starting or in full operation.
The thermal class selected and the rated power of the motor also
influence in this parameter.
Only a value of approximately 160 can be read if the motor is operating
in full load for over 2 hours with a current equal to the rated current
plus the service factor (In x F.S. @ 2h).
P050
0 to 250
Motor Thermal
[ - ]
Protection Status
1%
P085
0 to 3
Status of the Fieldbus
[ - ]
Communication Board
-
P085
Description
0
Off
1
Board inactive
2
Board active and Offline
3
Board active and Online
Indicates the status of the Fieldbus communication board.
Standard is disabled when board is not inserted.
For more details, refer to the Fieldbus Manual for the Soft-Starter
SSW-06.
Table 6.1
- Fieldbus communication board status
6.2 REGULATION PARAMETERS - P100 to P199
Used in the control by Voltage Ramp and Pump Controls, P202=0 or 2.
Sets the initial value of the rated voltage (%Un) that will be applied to
the motor according to Figure 6.1.
For more details about the programming and use, see Voltage Ramp
and Pump Control in P202.
The initial voltage is 0.5s after the Soft-Starter SSW-06 receives the
command to start the motor. This is the waiting time for the network
isolation contactor to start the power supply.
P101
Initial Voltage
25 to 90
[ 30 ]
1% Un of the Motor
P043
0 to 6553
Time Enabled
[ - ]
0.1 (<999.9)
1 (<6553)
Indicates the total number of hours that the Soft-Starter has
run
.
This value remains stored even when the Soft-Starter is turned OFF.
Indicates up to 6553 hours, rolls over to 0000.
If P204 is set to 3, P043 is reset to zero.
Start
P102
0,5s
0
P101
U(V)
Start
Figure 6.1 –
Initial time for motor start