CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
112
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Soft-Starter SSW-06 allows for the use of a torque pulse during the
starting process for loads that have high resistance during the starting
process.
Enabled through P520=1. The duration of this pulse may be adjusted
at P521.
This pulse will be applied according to the type of control selected at
P202:
- Voltage ramp: the voltage level may be set at P522.
- Current limit: the current level may be set at P523.
- Current Ramp: with adjustable current level.
NOTES!
1) Use this function only for specific applications, when so
required.
2) This function is not required for the Torque Control.
P520
(1)
0 or 1
Torque Pulse
[ 0=Inactive ]
at Start
-
P521
0.1 to 2
Pulse Time
[ 0.1 ]
at Start
0.1s
P522
70 to 90
Pulse Level of the
[ 70 ]
Starting Voltage
1 %Un of the motor
P523
300 to 700
Pulse Level of the
[ 500 ]
Starting Current
1 %In of the motor
Start
U(V)
100%Un
t(s)
P102
Disable
Enable
Voltage Ramp
0
P101
P522
P521
Start
I(A)
I Limit
t(s)
P102
Disable
Enable
Current Limit
0
P110
P523
P521
I Nominal