CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
78
Indicates Soft-Starter SSW-06 output current as percentage of the
rated current of the Soft-Starter (%In of the SSW-06) .
Precision of ± 2% for the full scale. (The full scale is 5x ln of the
SSW-06).
NOTE!
When the connection is used inside the delta of the motor
(P150=1), the indication of the current value will already be
multiplied by 1.73.
P001
0 to 999.9
Soft- Starter SSW-06
[ - ]
Current
0.1%
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Indicates Soft-Starter SSW-06 Output Current as percentage of the
motor rated current (%In of the motor).
Precision of ± 2% for the full scale. (The full scale is 5x ln of the
SSW-06).
NOTE!
When the connection is used inside the delta of the motor
(P150=1), the indication of the current value will already be
multiplied by 1.73.
P002
0 to 999.9
Motor Current
[ - ]
0.1%
Indicates the Soft-Starter SSW-06 output current in Ampere (A).
Precision of ± 2% for the full scale. (The full scale is 5x ln of the
SSW-06).
NOTE!
When the connection is used inside the delta of the motor
(P150=1), the indication of the current value will already be
multiplied by 1.73.
P003
0 to 9999.9
Motor Current
[ - ]
0.1A
Indicates the average True rms voltage of the tree input phases in
Volts (V).
Accuracy: ± 2V.
P004
0 to 999
Line Voltage
[ - ]
1V
Indicates the line frequency in Hertz (Hz).
Precision of ± 5% of the rated frequency of the supply network.
NOTE!
Only indicates network frequency when there is a voltage greater
than 20V rms in the power supply (R/ 1L1, S/ 3L2 and T/5L3).
P005
0 to 99
Line Frequency
[ - ]
1Hz
Indicates the actual Soft-Starter SSW-06 status:
0 = “rdy”
Soft-Starter is ready to be enabled;
8 = “Sub”
Soft-Starter under voltage fault;
9 = “Exx”
Soft-Starter fault;
1 = “ruP”
Soft-Starter is enabled according to “ramp up”;
2 = “FuLL”
Soft-Starter is enabled at “full voltage”;
3 = “PASS“
Soft-Starter is enabled with “By-pass”;
6 = “ECO”
Reserved;
4 = “rdo”
Soft-Starter is enabled according to “ramp down”;
5 = “br”
Soft-Starter is enabled according to “braking”;
6 = “rEv”
Soft-Starter is enabled according to “reversing”;
7 = “JOG”
Soft-Starter is enabled according to “jog”;
11 = “dly”
Soft-Starter awaiting the post “delay” stop time;
12 = “G.di”
Soft-Starter with “general disable”.