![WEG SSW-06.0085 Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/weg/ssw-06-0085/ssw-06-0085_user-manual_950611076.webp)
77
DETAILED PARAMETER DESCRIPTION
This Chapter describes in detail all Soft-Starter SSW-06 parameters. In
order to simplify the explanation, the parameters have been grouped by
characteristics and functions:
Symbols and definitions used in the text below:
(1)
Indicates that the parameter can only be changed when the Soft-Starter
SSW-06 is disabled (motor stopped).
(2)
Parameters not changed when programmed at Factory Default.
(P204=5).
6.1
ACCESS AND READ ONLY PARAMETERS - P000 to P099
This parameter opens the access to change the parameter values.
When values are set according to Factory Default [P200 = 1 (Password
is active)] to must set P000 = 5 to change parameter values, i. and.
the Password value is equal to 5.
To change the password to any other value (password 1), proceed as
follows:
(1)
Set P000=5 (current password) and P200= 0 (password inactive).
(2)
Press the key
.
(3)
Change P200 to 1 (password active).
(4)
Press the key
again: display shows: P000.
(5)
Press the key
again: display shows 5 (last password).
(6)
Use the keys
and
to change to the desired password
value (password 1).
(7)
Press the key
: display shows P000. From this moment on, the
new password becomes active. Thus, to change parameter content
P000 one must set to the new password. (Password 1).
P000
0 to 999
Access Parameter/
[0]
Password Value
-
Setting
Range
[Factory Setting]
Parameter
Unit
Description / Notes opens
Read Only Parameters
Variables that can only be viewed on the
display but not changed by the user.
Regulation Parameters
Programmable values used by the
Soft-Starter SSW-06 functions.
Configuration Parameters
These Parameters define the Soft-Starter
SSW-06 characteristics, the functions
which to be executed, as well as the
input/output functions of the control board.
Motor Parameters
Motor data that are indicated on the
motor nameplate.
Special Function Parameters
Here are included the parameters
related to special functions.
Protection Parameters
Here are included the parameters
related the actuation levels and
actuation time of the motor protection
CHAPTER