![WEG SSW-06.0085 Скачать руководство пользователя страница 88](http://html.mh-extra.com/html/weg/ssw-06-0085/ssw-06-0085_user-manual_950611088.webp)
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
89
This parameter is reserved for future software versions with hydraulic
pump control type. The current version has been developed for the
control of centrifugal hydraulic pump, considering quadratic motor
loads.
For more details about the Pump Control, see P202.
P130
(1)
0
Pump Control
[ 0=Pump ]
-
Range
[Factory Setting]
Parameter
Unit
Description / Notes
For more details about programming and application, refer to Torque
Control at P202.
P127
Action
1 (Constant)
P127 not used
2 (Linear)
P127 limits the torque when the motor is stopped
3 (Quadratic)
P127 limits the intermediate torque for the stop
P128
1 to 99
Time for Minimum
[ 50 ]
Stop Torque.
1% of P104
For more details about programming and application, refer to Torque
Control at P202.
P128
Action
1 (Constant)
P128 not used
2 (Linear)
P128 not used (time equal to 0)
3 (Quadratic)
P128 time for the intermediate torque limit for the stop process.
Here you can program the time for the intermediate stop torque, as
percent of the maximum time programmed at P104, when the
quadratic torque has been selected at P125.
Table 6.9
– Function of P127 according to P125
Table 6.10
– Function of P128 according to P125
P127
10 to 100
Minimum Stop
[ 50 ]
Torque
1% Tn of the Motor
Here you can program the initial torque limit or an intermediate torque
limit for the stop, when a linear torque or a quadratic torque has been
selected at P125.
Figure 6.9
– Start and Stop by Pump Control
U(V)
P101
0
P102
Start
100%Un
P103
P104
P105
t(s)
Stop
Disable
Enable
Pump Control
P140
(1)
0 or 1
External By-pass
[ 0=Inactive ]
Contactor
-
P140
Action
0 (Inactive)
Without external By-pass contactor
1 (Active)
With external By-pass contactor
Table 6.11
- External By-pass contactor
This function is enabled when the installation of an external By-pass
contactor is required that must be connected parallel to Soft-Starter
SSW-06.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]