SSW-06 - QUICK PARAMETER REFERENCE
10
Parameter
Description
Adjustable Range
Factory
Unit
User´s
Page
Setting
Setting
P042
Time Powered
0 to 65530
-
h
81
P043
Time Enabled
0 to 6553
-
h
82
P050
Motor Thermal Protection Status
0 to 250
-
%
82
P085
Fieldbus Communication Board Status
0=Off
-
-
82
1=Board Inactive
2=Board Active and Offline
3=Board Active and Online
REGULATION PARAMETERS P100 TO P199
Voltage Ramp
P101
Initial Voltage (% Un of the motor)
25 to 90
30
%
82
P102
Acceleration Ramp Time
1 to 999
20
s
83
P103
Deceleration Voltage Step
100=Inactive
100=Inactive
%
84
(% Un of the motor)
99 to 60
P104
Deceleration Ramp Time
0=Inactive
0=Inactive
s
84
1 to 299
P105
End Deceleration Voltage
30 to 55
30
%
84
(% Un of the Motor)
Current Limit
P110
Current Limit
150 to 500
300
%
84
(%In of the Motor current)
P111
Initial Current for the Current Ramp
150 to 500
150
%
85
(% In of the Motor)
P112
Time for the Current Ramp
1 to 99
20
%
85
(% of P102)
Torque Control
P120
(1)
Starting Torque Characteristics
1=Constant
1=Constant
-
86
2=Linear
3=Quadratic
P121
Initial Starting Torque (% Tn of Motor)
10 to 400
30
%
87
P122
End Starting Torque (% Tn of Motor)
10 to 400
110
%
87
P123
Minimum Starting Torque
10 to 400
27
%
87
(% Tn of the Motor)
P124
Time for the Minimum Start Torque
1 to 99
20
%
87
(% of P102)
P125
(1)
Stopping Torque Characteristics
1=Constant
1=Constant
-
88
2=Linear
3=Quadratic
P126
End Stop Torque (% Tn of the Motor)
10 to 100
20
%
88
P127
Minimum Stop Torque
10 to 100
50
%
89
(% Tn of the Motor)
P128
Time for the Minimum Stop Torque
1 to 99
50
%
89
(% of P104)
Pump Control
P130
(1)
Pump Control
0= Pump I
0= Pump I
-
89
1= Pump II
By-pass
P140
(1)
External By-pass Contactor
0=Inactive
0=Inactive
-
89
1=Active