CHAPTER 3 - INSTALLATION AND CONNECTION
38
3.2.3
Recommended Power/
Grounding Cables
The described specifications in tables 3,6 and 3,7 are valid only for the
following conditions:
Copper wires with PVC 70°C (158ºF) PVC insulation, for room
temperature of 40°C (104ºF) , installed in perforated and non-
agglomerated conduits
Naked or silver coared copper busbars with round edges and radius
equal to 1 mm with room temperature of 40°C (104ºF) and bus
temperature of 80°C (176ºF).
Obs.: When external By-pass contactors are applied, use the same
cables or busbar applied for the motor connection.
NOTE!
For correct cable dimensioning, consider the installation condition and
the maximum permitted line voltage drop.
Current
100% In
(A )
85
130
170
205
255
312
365
412
480
604
670
820
950
1100
1400
Model
SSW-06.0085
SSW-06.0130
SSW-06.0170
SSW-06.0205
SSW-06.0255
SSW-06.0312
SSW-06.0365
SSW-06.0412
SSW-06.0480
SSW-06.0604
SSW-06.0670
SSW-06.0820
SSW-06.0950
SSW-06.1100
SSW-06.1400
Cables
(mm²)
25
50
70
95
120
185
240
240
300
2 x 150
2 x 185
2 x 240
2 x 300
4 x 150
4 x 185
Bus
(mm x mm)
12 x 2
20 x 3
20 x 3
20 x 3
25 x 5
25 x 5
25 x 5
30x5
40x5
40x5
40x10
40x10
50x10
60x10
80x10
Grounding
Cables
(mm²)
10
25
35
50
70
95
120
120
150
150
185
240
300
2 x 150
2 x 185
Table 3.6
- Minimum specification of cables and busbars for standard
connection