CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
98
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Table 6.22
- FWD/REV selection
P231
0
1
2
Action
Inactive
By Contactor
JOG Only
“By Contactor”
This option enables the possibility of changing the direction of rotation
via contactors connected at the input power supply.
The new method implemented in the Soft-Starter SSW-06 allows the
use of only two contactors to change the motor direction of rotation
and isolate the power supply at the same time.
Possibility of changing the direction of rotation with inside delta mo-
tor connection.
When the motor is stopped the contactors are opened. When the
motor is enabled the specific contactor is enabled.
Figura 6.13
– Troca do sentido de giro via contator
NOTES!
1. Set P277=1 (FWQ/REV-K1) and P278=1 (FWQ/REV-K2)
before connecting the power supply.
2. The method used to start the motor to a new direction of
rotation will be the same as the one set to start the motor
at the first time.
3. The motor will start again only after the time set at P630
(time delay after starting).
4. See the recommended setup at items 3.3 and 3.3.8.
Enable
U(V)
100%Un
t(s)
0
100%Un
Start
Disable
P630
FWD/REV - K1 Closed
FWD/REV - K2 Closed
Start
P231
(1)
FWD/REV Selection
0 to 2
[ 0=Inactive ]
-