CHAPTER 3 - INSTALLATION AND CONNECTION
28
Figure 3.2 -
Free spaces for cooling
C
A
Y
B
B
Table 3.2
- Recommended free spaces
Air Flow Outlet
Air Flow Inlet
A
mm (in)
150 (5.90)
150 (5.90)
150 (5.90)
150 (5.90)
150 (5.90)
150 (5.90)
150 (5.90)
Model
SSW-06.0085
SSW-06.0130
SSW-06.0170
SSW-06.0205
SSW-06.0255
SSW-06.0312
SSW-06.0365
SSW-06.0412
SSW-06.0480
SSW-06.0604
SSW-06.0670
SSW-06.0820
SSW-06.0950
SSW-06.1100
SSW-06.1400
B
mm (in)
30 (1.18)
30 (1.18)
30 (1.18)
30 (1.18)
30 (1.18)
30 (1.18)
100 (3.93)
C
mm (in)
150 (5.90)
150 (5.90)
150 (5.90)
150 (5.90)
150 (5.90)
150 (5.90)
150 (5.90)
Y
mm (in)
50 (1.96)
50 (1.96)
50 (1.96)
50 (1.96)
50 (1.96)
50 (1.96)
50 (1.96)
When the Soft-Starter SSW-06 are installed in panels or closed metallic
boxes, adequate cooling is required to ensure that the temperature
around the inverter will not exceed the maximum allowed temperature.
See Dissipated Power in the table 3.4.