CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
102
P277
(1)
0 to 9
RL1 Relay Output
[ 1=in
Function
Operation ]
-
P278
(1)
0 to 9
RL2 Relay Output
[ 2=at Full
Function
Voltage ]
-
P279
(1)
0 to 9
RL3 Relay Output
[ 6=No
Function
Fault ]
-
Check the available options in Table 6.26.
The status of the digital outputs can be monitored in the Parameter
P013.
The digital output will be enabled when the function which has been
programmed for the digital output is true.
Figure 6.17 -
Status of the relay digital outputs when disabled.
“Not used”
= the digital outputs are disabled.
“In Operation”
= the output will be enabled instantly with the Soft-Starter
SSW-06 Enable command, and will only be disabled when the
Soft-Starter SSW-06 receives the command Disable, or when the end
of the deceleration ramp is reached, if programmed.
“Full Voltage”
= the output will be enabled when the Soft-Starter
SSW-06 reaches 100% Un and it will be disabled when the Soft-Starter
SSW-06 receives the command Disable.
“External By-pass”
= its operation is similar to the “Full Voltage”
operation, but it must be applied only when the use of an external
By-pass contactor is required. See P140 and the recommended setup
at items 3.3 and 3.3.12.
“FWD/REV-K1”
= This operation is similar to the “In Operation”, but it
must be enabled with forward motor direction of rotation. See P231
and the recommended setup at items 3.3 and 3.3.8.
“FWD/REV-K2”
= This operation is similar to the “In Operation”, but it
must be enabled with reverse motor direction of rotation. See P231
and the recommended setup at items 3.3 and 3.3.8.
“DC-Braking”
= The output will be enabled during the DC-Braking is
active. See P500 and the recommended setup at items 3.3 and 3.3.11.
The output will be enabled when DC-Braking is active. See P500 and
the recommended set-up at items 3.3 and 3.3.11.
Range
[Factory Setting]
Parameter
Unit
Description / Notess
DIx Parameter
DI1
P264
P265
P266
P267
P268
Function
(DI2)
(DI3)
(DI4)
(DI5)
(DI6)
Not used
-
0
0
0
0
0
Enable/Disable
-
-
-
-
-
or Start
Stop (Three wires)
-
1
-
-
-
-
General Enable
-
-
1
-
-
-
FWD/VER REV
-
-
-
1
1
1
Local/Remote
-
-
-
2
2
2
No external Error
-
-
-
3
3
3
JOG
-
-
-
4
4
4
Brake Off
-
-
-
5
5
5
Error Reset
-
2
2
6
6
6
Motor Thermistor
-
-
-
-
-
7
Table 6.25 -
Functions of the Digital Inputs
18
19
20
21
22
23
24
RL3
RL2
RL1
X1C