Centurion Water Heater- Edge [ii]: Install-Operation-Service
SECTION 2: INSTALLATION
OMM-0153_A
• 8/25/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 25 of 131
2.9 AC ELECTRICAL POWER WIRING
CENTURION Water Heaters are available with the following power options:
Model
Voltage
Phase
Amperage
CEN2000
208 V
3
/
60 Hz
20
CEN2000
460 V
3
/
60 Hz
15
2.9.1 Power Panel Locations
External AC power connection is made inside the Power Panel, located on the front of the unit,
behind the unit’s removable front panel.
Figure 2-12: Power Panel
Each unit must be connected to a dedicated electrical circuit.
NO OTHER DEVICES SHOULD
BE ON THE SAME ELECTRICAL CIRCUIT AS THE WATER HEATER
.
A switch must be installed on the electrical supply line, external to the unit, in an easily
accessible location to disconnect electrical service quickly and safely. DO NOT attach the
switch to sheet metal enclosures of the unit.
After placing the unit in service, the ignition safety shutoff device must be tested. If an external
electrical power source is used, the installed Water Heater must be electrically bonded to
ground in accordance with the requirements of the authority having jurisdiction. In the absence
of such requirements, the installation shall conform to National Electrical Code (NEC),
ANSI/NFPA 70 and/or the Canadian Electrical Code (CEC) Part I, CSA C22.1 Electrical Code.
2.9.2 Electrical Power Panel Internal Components
Remove the front panel to access the main Power Panel. Run the electrical service through the
opening above the Power Panel and make the connections to the Power Breaker in accordance
with the Power Panel cover label.
MAIN POWER PANEL
SECONDARY
POWER PANE
I/O BOARD
(Protector in place)