Watlow EZ-ZONE
®
RMC Module
•
92
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[SFn;B]
[SFn.b]
Counter (1 to 4)
Source Function B
Set the type of function
that will be used for the
counter load signal.
[none]
None (62)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[`lgC]
Logic (239)
[SoF;1]
Special Function Output
1 (1532)
[SoF;2]
Special Function Output
2 (1533)
[SoF;3]
Special Function Output
3 (1534)
[SoF;4]
Special Function Output
4 (1535)
[tMr]
Timer (244)
[`uAr]
Variable (245)
None
4162
[offset 40]
0x82 (130)
1 to 4
2
- - - -
30002
uint
RWES
[`Si;B]
[ Si.b]
Counter (1 to 4)
Source Instance B
Set the instance of the
function selected above.
1 to 24
1
4166
[offset 40]
0x82 (130)
1 to 4
4
- - - -
30004
uint
RWES
[`S2;B]
[ SZ.b]
Counter (1 to 4)
Source Zone B
Set the zone of the func-
tion selected above.
0 to 16
0
4170
[offset 40]
0x82 (130)
1 to 4
6
- - - -
30006
uint
RWES
[sas;b]
[SAS.b]
Counter (1 to 4)
Source Active State B
Set what output state
will indicate on.
[high]
High (37)
[LoW]
Low (53)
High
4182
[offset 40]
0x82 (130)
1 to 4
0x0C (12)
- - - -
30012
uint
RWES
[LoAd]
[LoAd]
Counter (1 to 4)
Load Value
Set the counter's initial
value.
0 to 9,999
0
4184
[offset 40]
0x82 (130)
1 to 4
(13)
215
30013
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S: