background image

Watlow  EZ-ZONE

®

  RMC  Module 

    85   

 

Chapter  4  Setup  Page

RMC Module  •  Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus 

Relative 

Address

CIP

Class 

Instance

Attribute

hex (dec)

Profibus 

Index

Parameter

ID

Data 

Type 

& Read/

Write

[`iP;1]

[ ip.1]

Linearization (1 to 4)

Input Point 1

Set the value that will 

be mapped to output 1.

-1,999.000 to 9,999.000

0.0

4534

[offset 70]

0x86 (134)

1 to 4

8

157

34008

float
RWES

[`oP;1]

[ op.1]

Linearization (1 to 4)

Output Point 1

Set the value that will 

be mapped to input 1.

-1,999.000 to 9,999.000

0.0

4554

[offset 70]

0x86 (134)

1 to 4

0x12 (18)

158

34018

float
RWES

[`iP;2]

[ ip.2]

Linearization (1 to 4)

Input Point 2

Set the value that will 

be mapped to output 2.

-1,999.000 to 9,999.000

1.0

4536

[offset 70]

0x86 (134)

1 to 4

9

159

34009

float
RWES

[`oP;2]

[ op.2]

Linearization (1 to 4)

Output Point 2

Set the value that will 

be mapped to input 2.

-1,999.000 to 9,999.000

1.0

4556

[offset 70]

0x86 (134)

1 to 4

0x13 (19)

160

34019

float
RWES

[`iP;3]

[ ip.3]

Linearization (1 to 4)

Input Point 3

Set the value that will 

be mapped to output 3.

-1,999.000 to 9,999.000

2.0

4538

[offset 70]

0x86 (134)

1 to 4

0xA (10)

161

34010

float
RWES

[`oP;3]

[ op.3]

Linearization (1 to 4)

Output Point 3

Set the value that will 

be mapped to input 3.

-1,999.000 to 9,999.000

2.0

4558

[offset 70]

0x86 (134)

1 to 4

0x14 (20)

162

34020

float
RWES

[`iP;4]

[ ip.4]

Linearization (1 to 4)

Input Point 4

Set the value that will 

be mapped to output 4.

-1,999.000 to 9,999.000

3.0

4540

[offset 70]

0x86 (134)

1 to 4

0xB (11)

163

34011

float
RWES

[`oP;4]

[ op.4]

Linearization (1 to 4)

Output Point 4

Set the value that will 

be mapped to input 4.

-1,999.000 to 9,999.000

3.0

4560

[offset 70]

0x86 (134)

1 to 4

0x15 (21)

164

34021

float
RWES

[`iP;5]

[ ip.5]

Linearization (1 to 4)

Input Point 5

Set the value that will 

be mapped to output 5.

-1,999.000 to 9,999.000

4.0

4542

[offset 70]

0x86 (134)

1 to 4

0xC (12)

165

34012

float
RWES

[`oP;5]

[ op.5]

Linearization (1 to 4)

Output Point 5

Set the value that will 

be mapped to input 5.

-1,999.000 to 9,999.000

4.0

4562

[offset 70]

0x86 (134)

1 to 4

0x16 (22)

166

34022

float
RWES

[`iP;6]

[ ip.6]

Linearization (1 to 4)

Input Point 6

Set the value that will 

be mapped to output 6.

-1,999.000 to 9,999.000

5.0

4544

[offset 70]

0x86 (134)

1 to 4

0xD (13)

167

34013

float
RWES

[`oP;6]

[ op.6]

Linearization (1 to 4)

Output Point 6

Set the value that will 

be mapped to input 6.

-1,999.000 to 9,999.000

5.0

4564

[offset 70]

0x86 (134)

1 to 4

0x17 (23)

168

34023

float
RWES

Note: 

Some values will be rounded off to fit in the four-character display . 

Full values can be read with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and 

above .

R: Read 

W: Write 

E: 

EEPROM

S: 

User Set

Содержание EZ-ZONE RMC

Страница 1: ...r s Guide Registered Company Winona Minnesota USA ISO 9001 TOTAL 3Y earWarranty CUSTOMER SATISFACTION EZ ZONE RMC Control Module Control Module 1241 Bundy Boulevard Winona Minnesota USA 55987 Phone 1...

Страница 2: ...ls on Directives and Standards used for Compliance Unit has been reviewed and ap proved by Factory Mutual as a Temperature Limit Device per FM Class 3545 standard See www fmglobal com Unit has been re...

Страница 3: ...ir work 5 To return products that are not defective goods must be in new condition in the original boxes and they must be returned with in 120 days of receipt A 20 percent restocking charge is applied...

Страница 4: ...u Pages 34 Chapter 3 Operations Pages 36 Analog Input Menu 38 Process Value Menu 38 Digital Input Output Menu 39 Action Menu 40 Limit Menu 40 Monitor Menu 40 Loop Menu 41 Alarm Menu 43 Current Menu 45...

Страница 5: ...118 Chapter 5 Profiling Page 121 How to Setup and Start a Profile 121 Chapter 6 Factory Pages 139 Custom Setup Menu 140 Security Setting Menu 141 Security Setting Menu 143 Diagnostics Menu 143 Calibr...

Страница 6: ...Table of Contents Software Configuration 164 Function Block Descriptions 167 Chapter 8 Appendix 212 Modbus Programmable Memory Blocks 212 Control Module Specifications 214 Index 218 How to Reach Us 22...

Страница 7: ...oads Communication Capabilities Supports network connectivity to a PC or PLC Watlow Standard Bus or Modbus RTU Provides plug and play capabilities with Remote User Interface RUI s and RMA module Free...

Страница 8: ...system reliability and lowers wiring costs Factory Mutual FM Approved Safety Limit Increases user and equipment safety for over under temperature conditions Supports SEMI S2 specification Agency Appro...

Страница 9: ...264 Vac to 24Vdc 91 watts 2 RMC Module can provide 1 to 4 control loops limits or CT inputs 1 to 9 inputs various types 1 to 12 outputs various types Modbus RTU communications As can be seen above the...

Страница 10: ...when the condition that caused the alarm goes back to a non alarm state if the alarm latching prompt is set to non latching Setup Page Alarm Menu Keep in mind that a function is a user programmed inte...

Страница 11: ...re available protocols 1 EtherNet IP and or Modbus TCP 2 DeviceNet 3 Modbus RTU Slot C Slot C Slot E RM Access RM Control Power Supply PLC RMC Module Connected to an Operator Inter face Terminal OIT t...

Страница 12: ...ot shown All of these slots are not always used on all modules On the face of the module there is a button white circle under the Zone address 5 that when pushed and held has the following functions 1...

Страница 13: ...Open Collector 5A Mechanical Relay Form C Process or 0 5A Solid State Relay Form A Output 1 3 5 Digital Input or output 7 12 Switch contact or volts dc Digital Output or input 7 12 Switch contact or...

Страница 14: ...nt Transformer Sense CT Limit or PID Controller Slot A B D or E optional EIA 485 Communications Standard Bus optional Modbus RTU Inter module Bus Class 1 Div II not available with mechanical relay out...

Страница 15: ...e will change slightly based on the type of connector used 147 07 mm 5 8 in 101 60 mm 4 00 in 44 45 mm 1 75 in 51 56 mm 2 03 in 75 08 mm 3 0 in 165 mm 6 50 in Module Removal Displacement Latch in open...

Страница 16: ...mm 0 69 in 60 45 mm 2 38 in 35 81 mm 1 41 in 35 05 mm 1 38 in 32 77 mm 1 29 in Chassis Mount Front View Module Removed Screw Connection Pattern Recommended chassis mount hardware 1 8 screw 3 4 long 2...

Страница 17: ...4 in Power Supply Specifications DSP 30 DSP60 DSP100 AC Input Volt age Range VAC 90 264VAC Class II double in sulated No ground connection required Input Fre quency Hz 47 63Hz DC Input Volt age range...

Страница 18: ...further engage the bottom edge of the rail with an over center snap action latch The red locking tab protrudes from the bot tom side of the back plane assembly Installing Multiple Modular Backplane C...

Страница 19: ...wdriver upwards When released the tab will move downward and the connector can then be lifted up off of the DIN rail Module Removal To remove a module from the Modular Backplane Connector find the red...

Страница 20: ...valid Slot E RMCxxxxxxx C xxxx Outputs Switched dc Open Collector Outputs 1 3 5 and 7 1 2 3 4 5 6 7 8 X1 W1 Y1 X3 W3 Y3 X5 W5 Y5 X7 W7 Y7 common dc open collector dc Switched DC Open Collector Part Di...

Страница 21: ...xxx Output 3 RMCxxx G M S T Y Z xxxxxxxx Output 4 RMCxxx G M S T Y Z xxxxxxxx Output 5 RMCxxxxx G M S T Y Z xxxxxx Output 6 RMCxxxxx G M S T Y Z xxxxxx Output 7 RMCxxxxxxx G M S T Y Z xxxx Output 8 RM...

Страница 22: ...Watlow EZ ZONE RMC Module 19 Chapter 2 Install and Wire Slot A Slot E Slot D Slot B RMC Front View Standard Connector 98 99 power...

Страница 23: ...ts Controller Low Voltage Power Bus Mechanical Relay Solid State Relay NO ARC Relay Outputs Low voltage Isolation 42V peak Safety Isolation 1 528V ac Safety Isolation No Isolation No Isolation Low vol...

Страница 24: ...ption 7 Watts maxi mum 31 Watts maximum power available for P S part 0847 0299 0000 60 Watts maximum power available for P S part 0847 0300 0000 91 Watts maximum power available for P S part 0847 0301...

Страница 25: ...oncentrations of flammable sub stances Watlow EZ ZONE RMC Module 22 Chapter 2 Install and Wire Input 1 2 3 4 Thermistor RMC Part Digits 4 6 8 10 S_ R_ Slot A B D E 20 M input impedance Input 1 RMC 2 4...

Страница 26: ...not disconnect while the circuit is live or unless the area is known to be free of ignitable concentrations of flammable sub stances Warning Explosion Hazard Dry contact closure Digital Inputs shall...

Страница 27: ...l relay solid state relay or open collector output options requires use of an R C suppressor Digital Inputs Outputs 7 through 12 RMC Part Digit 11 is C Common Collector out Collector out B7 D7 D8 D9 D...

Страница 28: ...n Hazard Do not disconnect while the circuit is live or unless the area is known to be free of ignitable concentrations of flammable sub stances Quencharc Note Switching pilot duty inductive loads rel...

Страница 29: ...ignitable concentrations of flammable sub stances Watlow EZ ZONE RMC Module 26 Chapter 2 Install and Wire Quencharc Note Switching pilot duty inductive loads re lay coils solenoids etc with the me ch...

Страница 30: ...C and D or Non Hazardous locations only Temperature Code T4 Warning Explosion Hazard Substitution of component may impair suitability for CLASS I DIVISION 2 Warning Explosion Hazard Do not disconnect...

Страница 31: ...ing Explosion Hazard Do not disconnect while the circuit is live or unless the area is known to be free of ignitable concentrations of flammable sub stances Watlow EZ ZONE RMC Module 28 Chapter 2 Inst...

Страница 32: ...CF CD CE CZ CX CY Wire T R to the A terminal of the EIA 485 port Wire T R to the B terminal of the EIA 485 port Wire common to the common terminal of the EIA 485 port Do not route network wires with...

Страница 33: ...1 start bit 1 stop bit PC Software Protocol Standard Bus EZ Configurator D E A B D E A B S M 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 RM 1 EZ ZONE R Slot C 98 99 CC CA CB CZ CX CY 98 99 CC CA CB CZ CX...

Страница 34: ...to 1 msec Failure to make this change may cause communication loss between the PC running ZE ZONE Configurator software and the control To modify Latency Timer settings follow the steps below 1 Navig...

Страница 35: ...equire a termina tion resistor at both ends of the network A Network Using Watlow s Standard Bus and an RUI Gateway A B com A B common power A B common power power power EZ ZONE PM EZ ZONE ST ST_ _ B...

Страница 36: ...upply The top DIN rail now has the following modules 2 RMC modules consumes 14W 1 RMA consumes 4W 11 RME modules consumes 77W As it can now be understood the total power require ment exceeds 91W In th...

Страница 37: ...ology several characters displayed need some interpretation see the list below 1 1 0 0 i i r r 2 2 a A j J s S 3 3 h b H K t t 4 4 c C c L L U u 5 5 d d m M u v 6 6 e E n n w W 7 7 f F o o y y 8 8 g g...

Страница 38: ...0 low order bytes and 361 high order bytes The Modbus specification does not dictate which register should be high or low order so Watlow provides the user the ability to swap this order Setup Page Co...

Страница 39: ...CUrr oPEr Current Menu 1 CUrr Current 1 to 4 C hi High Set Point C Lo Low Set Point CU r RMS Read C Er Error h Er Heater Error Lnr oPEr Linearization Menu 1 Lnr Linearization 1 to 4 Su A Source Value...

Страница 40: ...ue E oFSt Offset o u Output Value SoF oPEr Special Output Function Menu 1 SoF Special Output Function 1 to 4 Su A Source Value A Su b Source Value B ou 1 Output Value 1 ou 2 Output Value 2 ou 3 Output...

Страница 41: ...i CA Analog Input 1 to 4 Calibration Offset Offset the input reading to compensate for lead wire resistance or other factors that cause the in put reading to vary from the actual process value 1 999 0...

Страница 42: ...3 float RWES o u o u Process Value 1 to 4 Output Value View the value of this function block s output 1 999 000 to 9 999 000 F or units 1 128 000 to 5 537 000 C 3442 offset 70 0x7E 126 1 to 4 0x16 22...

Страница 43: ...et Point Set the high process value that will trigger the limit 1 999 000 to 9 999 000 F or units 1 128 000 to 5 537 000 C 0 0 F or units 18 0 C 726 offset 30 0x70 112 1 to 4 4 39 12004 float RWES No...

Страница 44: ...B 107 1 to 4 0x15 21 48 7021 uint RWES C M C M Control Loop 1 to 4 Control Mode Select the method that this loop will use to control off Off 62 AUto Auto 10 MAn Manual 54 Auto 2220 offset 70 0x97 151...

Страница 45: ...ES C Pb C Pb Control Loop 1 to 4 Cool Proportional Band Set the PID propor tional band for the cool outputs 0 001 to 9 999 000 F or units 0 001 to 5 555 000 C 25 0 F or units 14 0 C 2232 offset 70 0x9...

Страница 46: ...97 151 1 to 4 0x19 25 8048 uint R No Dis play Control Loop 1 to 4 Error Clear Write to this register to clear loop error Clear 129 Ignore 204 Ignore 2270 offset 70 0x97 151 1 to 4 0x1A 26 8049 uint W...

Страница 47: ...sir A Sir Alarm 1 to 8 Alarm Silence Re quest Write to this register to silence an alarm 0 1766 offset 60 0x6D 109 1 to 8 0xE 14 33 9014 uint W a st A St Alarm 1 to 8 Alarm State Current state of ala...

Страница 48: ...115 1 to 4 2 15002 uint R h Er h Er Current 1 to 4 Heater Error View the cause of the most recent load fault monitored by the cur rent transformer nonE None 61 high High 37 Low Low 53 1384 offset 50 0...

Страница 49: ...o 4 Source Value B View the value of Source B 1 999 000 to 9 999 000 F or units 1 128 000 to 5 537 000 C 4014 offset 40 0x80 128 1 to 4 8 28008 float R o u o v Compare 1 to 4 Output Value View the val...

Страница 50: ...to tal count 0 to 9 999 4188 offset 40 0x82 130 1 to 4 0xF 15 217 30015 uint R Su A Su A Counter 1 to 4 Source Value A View the value of Source A off Off 62 on On 63 4172 offset 40 0x82 130 1 to 4 7...

Страница 51: ...t R Su F Su F Logic 1 to 4 Source Value F View the value of Source F off Off 62 on On 63 3738 offset 80 0x7F 127 1 to 4 0x1E 30 27030 uint R Su g Su g Logic 1 to 4 Value Source G View the value of Sou...

Страница 52: ...2878 offset 70 0x7D 125 1 to 8 0x14 20 25020 uint R oFSt oFSt Math 1 to 8 Offset Set an offset to be ap plied to this function s output 1 999 000 to 9 999 000 F or units 1 128 000 to 5 537 000 C 0 288...

Страница 53: ...to 9 999 000 F or units 1 128 000 to 5 537 000 C 4982 offset 80 0x87 135 1 to 4 0xC 12 35012 float R No Dis play Special Output Function 1 to 4 Error 2 View reported cause for output malfunction None...

Страница 54: ...eable personnel and with caution Changing parameters via the Profile Status Menu will not change the stored profile but will have an immediate impact on the profile that is running Changes made to pro...

Страница 55: ...the target set point of the current step 1 999 000 to 9 999 000 F or units 1 128 000 to 5 537 000 C 0 0 F or units 18 0 C 5376 0x7A 122 1 0x31 49 22049 float RW t SP4 t SP4 Profile Status Target Set...

Страница 56: ...Auto 10 Manual 54 5372 0x7A 122 1 0x2F 47 22047 uint R hoUr hoUr Profile Status Hours Step time remaing in hours 0 to 99 0 5434 0x7A 122 1 0x4E 78 22078 uint RW min Min Profile Status Minutes Step ti...

Страница 57: ...t value of analog source 4 1999 000 to 9999 000 5420 0x7A 122 1 0x47 71 22071 float R Ent1 Ent1 Profile Status Active Event Out put 1 View or change the event output states off Off 62 on On 63 Off 530...

Страница 58: ...63 Off 5320 0x7A 122 1 0x15 21 22021 uint RW JC JC Profile Status Jump Count Remain ing View the jump counts remaining for the cur rent loop In a profile with nested loops this may not indicate the a...

Страница 59: ...ource Instance A S2 A Source Zone A l Cr Clear Request l st Status Loop Set Control Loop Menu 1 Loop Control Loop 1 to 4 SFn A Source Function A is A Source Instance A h Ag Heat Algorithm C Ag Cool Al...

Страница 60: ...7 Input Point 7 op 7 Output Point 7 ip 8 Input Point 8 op 8 Output Point 8 ip 9 Input Point 9 op 1 Output Point 9 ip 10 Input Point 10 op 10 Output Point 10 CPE Set Compare Menu 1 CPE Compare 1 to 4...

Страница 61: ...Usr s User Settings Save Usr r User Settings Restore PRo Set Profile Menu PRo Profile r typ Ramping Type P typ Profile Type gSE Guaranteed Soak Enable gsd1 Guaranteed Soak Deviation 1 gsd2 Guaranteed...

Страница 62: ...f leads on the RTD wired to this input 2 2 1 3 3 2 2 372 offset 90 0x68 104 1 to 4 7 4007 uint RWES Unit Unit Analog Input 1 to 4 Units Set the type of units the sensor will measure A tP Absolute Temp...

Страница 63: ...1 b Curve B 1452 C Curve C 1453 CUSt Custom 180 Curve A 434 offset 90 0x68 104 1 to 4 0x26 38 4038 uint RWES r r r r Analog Input 1 to 4 Resistance Range Set the maximum resis tance of the thermistor...

Страница 64: ...no error 61 when reading this value using a field bus protocol If an error exists the last known value prior to the er ror occurring will be returned 1 999 000 to 9 999 000 F or units 1 128 000 to 5...

Страница 65: ...nput 3400 offset 70 0x7E 126 1 to 4 1 26001 uint RWES Si A Si A Process Value 1 to 4 Source Instance A Set the instance of the function selected above 1 to 4 3410 offset 70 0x7E 126 1 to 4 6 26006 uin...

Страница 66: ...0 3424 offset 70 0x7E 126 1 to 4 0x0D 13 26013 uint RWES SFn d SFn d Process Value 1 to 4 Source Function D Set the type of function that will be used for this source nonE None 61 Ai Analog Input 142...

Страница 67: ...Instance E Set the instance of the function selected above 1 to 24 1 3418 offset 70 0x7E 126 1 to 4 0xA 10 26010 uint RWES s2 E SZ E Process Value 1 to 4 Source Zone E Set the zone of the func tion s...

Страница 68: ...lue 1 4 Barometric Pressure If Process Value function is set for Wet Bulb Dry Bulb define pressure value used for humidity calculation 10 0 to 16 0 14 7 3458 offset 70 0x7E 126 1 to 2 0x1E 30 26030 fl...

Страница 69: ...gic 239 lnr Linearization 238 mat Math 240 pu Process Value 241 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Ou...

Страница 70: ...12 3 86 6003 float RWES o Lo o Lo Digital Output 7 to 12 Low Power Scale The power output will never be less than the value specified and will represent the value at which output scaling begins 0 0 t...

Страница 71: ...Alarms to Non alarm State 220 F AL Force Alarm to Occur 218 idLE Idle Set Point 107 tUnE Tune 98 MAn Manual 54 oFF Switch Control Loop Off 90 r En Remote Set Point En able 216 t dA TRU TUNE Disable 2...

Страница 72: ...Si A Si A Action 1 to 8 Source Instance A Set the instance of the function selected above 1 to 24 1 1582 offset 20 0x6E 110 1 to 8 2 10002 uint RWES S2 A SZ A Action 1 to 8 Source Zone A Set the zone...

Страница 73: ...LL S Limit 1 to 4 Low Set Point Set the low process value that will trigger the limit 1 999 000 to 9 999 000 F or units 1 128 000 to 5 537 000 C 0 0 F or units 18 0 C 724 offset 30 0x70 112 1 to 4 3 3...

Страница 74: ...ystem oFF Off 62 Cr A Non linear Curve 1 214 Cr b Non linear Curve 2 215 Off 2228 offset 70 0x97 151 1 to 4 5 8038 uint RWES h Pb h Pb Control Loop 1 to 4 Heat Proportional Band Set the PID propor tio...

Страница 75: ...ing outputs are active when the process value is near the set point A positive value keeps heating and cooling outputs from fighting each other 1 000 0 to 1 000 0 F or units 556 to 556 C 0 0 2238 offs...

Страница 76: ...remote set point no No 59 YES Yes 106 No 2540 offset 80 0x6B 107 1 to 4 0x15 21 48 7021 uint RWES SFn b SFn b Control Loop 1 to 4 Source Function B Set the function that will provide the remote set po...

Страница 77: ...han 75 and stable otherwise 0 14 MAn Manual Power sets output power to Fixed Power setting 54 USEr User sets output power to last open loop set point the user entered 100 User 2524 offset 80 0x6B 107...

Страница 78: ...to 4 Profiling Enable Enable this loop to run profiles no No 59 YES Yes 106 No 2552 offset 80 0x6B 107 1 to 4 0x1B 27 7027 uint RWES L SP L SP Control Loop 1 to 4 Low Set Point Set the minimum value...

Страница 79: ...to 4 6 55 7006 float RWES o SP o SP Control Loop 1 to 4 Open Loop Set Point Set a fixed level of output power when in manual open loop mode 100 0 to 100 0 heat and cool 0 to 100 0 heat only 100 0 to...

Страница 80: ...nt Out E 247 Ent F Profile Event Out F 248 Ent g Profile Event Out G 249 Ent h Profile Event Out H 250 FUn Function Key 1001 lgC Logic 239 lnr Linearization 238 mat Math 240 pu Process Value 241 SoF 1...

Страница 81: ...ch relay NO ARC 1024 offset 30 0x6A 106 1 to 8 3 6003 float RWES o Lo o Lo Output Digital 1 to 8 Low Power Scale The power output will never be less than the value specified and will represent the val...

Страница 82: ...S Fi Fi Output Process 1 3 5 or 7 Function Instance Set the instance of the function selected above 1 to 16 1 846 1 894 3 942 5 990 7 0x76 118 1 to 4 4 98 18004 uint RWES S2 A ZS A Output Process 1 3...

Страница 83: ...852 1 900 3 948 5 996 7 0x76 118 1 to 4 7 105 18007 float RWES Alm Set Alarm Menu A ty A ty Alarm 1 to 8 Type Select whether the alarm trigger is a fixed value or will track the set point oFF Off 62 P...

Страница 84: ...rm 66 Close On Alarm 1748 offset 60 0x6D 109 1 to 8 5 25 9005 uint RWES A Sd A Sd Alarm 1 to 8 Sides Select which side or sides will trigger this alarm both Both 13 high High 37 LoW Low 53 Both 1746 o...

Страница 85: ...L Alarm 1 to 8 Blocking Select when an alarm will be blocked After startup and or after the set point changes the alarm will be blocked until the process value enters the normal range oFF Off 62 Str S...

Страница 86: ...t 1 to 4 Read Enable Use Current Read En able to display solid state relay SSR failure and heater failure mes sages on the RUI re mote user interface no No 59 yes Yes 106 no 1386 offset 50 0x73 115 1...

Страница 87: ...r Linearization 238 MAt Math 240 Pu Process Value 241 SP C Set Point Closed Con trol Loop 242 SP o Set Point Open Control Loop 243 uAr Variable 245 None 4520 offset 70 0x86 134 1 to 4 1 155 34001 uint...

Страница 88: ...fset 70 0x86 134 1 to 4 0x14 20 162 34020 float RWES iP 4 ip 4 Linearization 1 to 4 Input Point 4 Set the value that will be mapped to output 4 1 999 000 to 9 999 000 3 0 4540 offset 70 0x86 134 1 to...

Страница 89: ...utput Point 9 Set the value that will be mapped to input 9 1 999 000 to 9 999 000 8 0 4570 offset 70 0x86 134 1 to 4 0x1A 26 174 34026 float RWES iP 10 ip 10 Linearization 1 to 4 Input Point 10 Set th...

Страница 90: ...t 40 0x80 128 1 to 4 5 28005 uint RWES SFn B SFn b Compare 1 to 4 Source Function B Set the type of function that will be used for this source This represents the timer reset signal nonE None 61 Ai An...

Страница 91: ...mer 1 to 4 Source Function A Set the type of function that will be used for this source This represents the timer run signal none None 62 ALM Alarm 6 CPE Compare 230 Ctr Counter 231 dio Digital I O 11...

Страница 92: ...ntrol Loop 161 CPE Compare 230 Ctr Counter 231 dio Digital I O 1142 Ent A Profile Event Out A 233 Ent b Profile Event Out B 234 Ent C Profile Event Out C 235 Ent d Profile Event Out D 236 Ent E Profil...

Страница 93: ...f a second 0 to 9 999 000 0 1 4344 offset 50 0x83 131 1 to 4 0xD 13 224 31013 float RWES LEu LEv Timer 1 to 4 Active Level Set which output state will indicate on high High 37 LoW Low 53 High 4346 off...

Страница 94: ...tput 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Timer 244 uAr Variable 245 None 4160 offset 40 0x82 130 1 to 4 1 30001 uint RWES Si A Si A Counter 1 to 4 Sour...

Страница 95: ...l Function Output 4 1535 tMr Timer 244 uAr Variable 245 None 4162 offset 40 0x82 130 1 to 4 2 30002 uint RWES Si B Si b Counter 1 to 4 Source Instance B Set the instance of the function selected above...

Страница 96: ...82 130 1 to 4 0x11 17 218 30017 uint RWES LgC Set Logic Menu Fn Fn Logic 1 to 4 Function Set the operator that will be used to compare the sources oFF Off 62 And And 1426 nAnd Nand 1427 or Or 1442 nor...

Страница 97: ...lim Limit 126 lgC Logic 239 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Timer 244 uAr Varia...

Страница 98: ...ction Key 1001 lim Limit 126 lgC Logic 239 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Timer...

Страница 99: ...ction Key 1001 lim Limit 126 lgC Logic 239 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Timer...

Страница 100: ...ction Key 1001 lim Limit 126 lgC Logic 239 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Timer...

Страница 101: ...nction Key 1001 lim Limit 126 lgC Logic 239 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Time...

Страница 102: ...ction Key 1001 lim Limit 126 lgC Logic 239 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Timer...

Страница 103: ...nction Key 1001 lim Limit 126 lgC Logic 239 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Time...

Страница 104: ...ction Key 1001 lim Limit 126 lgC Logic 239 SoF 1 Special Function Output 1 1532 SoF 2 Special Function Output 2 1533 SoF 3 Special Function Output 3 1534 SoF 4 Special Function Output 4 1535 tMr Timer...

Страница 105: ...1378 MAH Maximum 1379 root Square Root 1380 hoLd Sample and Hold 1381 alt Pressure to Altitude 1649 dew Dewpoint 1650 Off 2880 offset 70 0x7D 125 1 to 8 0x15 21 128 25021 uint RWES SFn A SFn A Math 1...

Страница 106: ...1 to 24 1 2852 offset 70 0x7D 125 1 to 8 7 25007 uint RWES S2 B SZ b Math 1 to 8 Source Zone B Set the zone of the func tion selected above 0 to 16 0 2862 offset 70 0x7D 125 1 to 8 0xC 12 25012 uint R...

Страница 107: ...73 Lnr Linearization 238 MAt Math 240 Pu Process Value 241 SP C Set Point Closed Con trol Loop 242 SP o Set Point Open Control Loop 243 uAr Variable 245 None 2846 offset 70 0x7D 125 1 to 8 4 25004 ui...

Страница 108: ...E Set the instance of the function selected above 1 to 24 1 2858 offset 70 0x7D 125 1 to 8 0xA 10 25010 uint RWES s2 E SZ E Math 1 to 8 Source Zone E Set the zone of the func tion selected above 0 to...

Страница 109: ...units set units of mea sure for conversion psi Pressure Units 1671 pasc Pascal 1674 atm Atmosphere 1675 mbr mbar 1672 torr Torr 1673 Pressure Units 2898 offset 70 0x7D 125 1 to 8 0x1E 30 25030 uint RW...

Страница 110: ...e zone of the func tion selected above 0 to 16 0 4968 offset 80 0x87 135 1 to 4 5 35005 uint RWES SFn b SFn b Special Output 1 to 4 Source Function B Set the type of function that will be used for thi...

Страница 111: ...ion whether the compressor will soon be required Set Power On Level 2 and Power Off Level 2 to the Source B values that will switch the compressor on and off 100 0 to 100 0 0 4998 offset 80 0x87 135 1...

Страница 112: ...st ments less accurate and the wear on the mechanism 1 0 to 100 0 2 5008 offset 80 0x87 135 1 to 4 0x19 25 193 35025 float RWES o S1 o S1 Special Output 1 to 4 Output 1 Size If Function is set to Se q...

Страница 113: ...in Linear 1509 Pro Progressive 1510 Linear 5012 offset 80 0x87 135 1 to 4 0x1B 27 35027 uint RWES uAr Set Variable Menu tyPE tyPE Variable 1 to 8 Data Type Set the variable s data type AnLg Analog 121...

Страница 114: ...tings Restore Replace all of this con troller s settings with another set FCty Factory 31 none None 61 SEt1 User Set 1 101 SEt2 User Set 2 102 None 24 0x65 101 1 0xD 13 117 1013 uint RWE PRo Set Profi...

Страница 115: ...oak De viation 3 Set the value of the deviation band that will be used in all profile step types The process value for control loop 3 must enter the deviation band before the step can proceed 0 0 to 9...

Страница 116: ...ompare 230 Ctr Counter 231 dio Digital I O 1142 Ent A Profile Event Out A 233 Ent b Profile Event Out B 234 Ent C Profile Event Out C 235 Ent d Profile Event Out D 236 Ent E Profile Event Out E 247 En...

Страница 117: ...Ent E Profile Event Out E 247 Ent F Profile Event Out F 248 Ent g Profile Event Out G 249 Ent h Profile Event Out H 250 FUn Function Key 1001 lgC Logic 239 tMr Timer 244 uAr Variable 245 None 5324 0x7...

Страница 118: ...Ent E Profile Event Out E 247 Ent F Profile Event Out F 248 Ent g Profile Event Out G 249 Ent h Profile Event Out H 250 FUn Function Key 1001 lgC Logic 239 tMr Timer 244 uAr Variable 245 None 5326 0x7...

Страница 119: ...Instance D Set the instance of the function selected above 1 to 24 1 5336 0x7A 122 1 0x1D 29 22029 uint RWE S2 D SZ D Profile Source Zone D Set the zone of the func tion selected above 0 to 16 0 5344...

Страница 120: ...r Variable 245 None 5392 0x7A 122 1 0x39 57 22057 uint RWE Si F Si F Profile Source Instance F Set the instance of the function selected above 1 to 24 1 5400 0x7A 122 1 0x3D 61 22061 uint RWE S2 F SZ...

Страница 121: ...Linearization 238 MAt Math 240 Pu Process Value 241 SP C Set Point Closed Con trol Loop 242 SP o Set Point Open Control Loop 243 uAr Variable 245 None 5396 0x7A 122 1 0x3B 59 22059 uint RWE Si h Si h...

Страница 122: ...bit words in the floating point values Note Used by Modbus RTU protocol hiLo Word High Low 1330 Lohi Word Low High 1331 Low High 2828 0x96 150 1 5 17043 uint RWE C_F C_F Communications Display Units...

Страница 123: ...Dis play Communications Comm Units Select which scale to use for temperature over comms F 30 C 15 F 2830 17050 uint RWE Note Some values will be rounded off to fit in the four character display Full v...

Страница 124: ...point where this condition must be met before the profile can proceed Control Mode Enable if changed to on will allow the loops control mode to be changed through the profile Wait for Mode determines...

Страница 125: ...n the screen shot below Prior to moving on it would be beneficial to point out see graphic on previous page that if it is desired to config ure a wait for process or event step within any given profil...

Страница 126: ...ed Soak Enable 4 SS Subroutine Step SC Subroutine Count JS Jump Step JC Jump Count EnD End Type Ent1 Event 1 Ent2 Event 2 Ent3 Event 3 Ent4 Event 4 Ent5 Event 5 Ent6 Event 6 Ent7 Event 7 Ent8 Event 8...

Страница 127: ...et the control mode for this loop AUto Auto 10 oFF Off 62 MAn Manual 54 Auto 5492 offset 100 0x79 121 1 to 250 0x1B 27 21027 uint RWE t SP1 t SP1 Step 1 to 250 Target Set Point Loop 1 If step type is...

Страница 128: ...000 C per min ute 0 0 5450 offset 100 0x79 121 1 to 250 6 21006 float RWE P E1 P E1 Step 1 to 250 Step Wait For Pro cess Enable 1 If step type is Wait for Process or Event select whether process valu...

Страница 129: ...250 0x20 32 21032 float RWE P E4 P E4 Step 1 to 250 Step Wait For Pro cess Enable 4 If step type is Wait for Process or Event select whether process value must be Less Than or Greater Than the value...

Страница 130: ...E1 Step 1 to 250 Guaranteed Soak Enable 1 Select if profile should pause while process 1 deviates from devia tion band oFF Off 62 on On 63 Off 5522 offset 100 0x79 121 1 to 250 0x2A 42 21042 uint RWE...

Страница 131: ...et point 100 User 5466 offset 100 0x79 121 1 to 250 0xE 14 21014 uint RWE Ent1 Ent1 Step 1 to 250 Event 1 Select whether output programmed as Pro file Event Out A is on unchanged or off dur ing this s...

Страница 132: ...ged 1557 on On 63 Un changed 5480 offset 100 0x79 121 1 to 250 0x15 21 21021 uint RWE S typ S typ Subroutine Step 1 to 150 Step Type Select a step type UStP Unused Step 50 SoAH Soak 87 W PE Wait For P...

Страница 133: ...99 000 F or units 1 128 000 to 5 537 000 C 0 0 30454 offset 86 0x69 105 1 to 150 8 5008 float t SP4 t SP4 Subroutine Step 1 to 150 Target Set Point Loop 4 If step type is Time or State enter set point...

Страница 134: ...Than 1436 g t Greater Than 1435 Off 30490 offset 86 0x69 105 1 to 150 0x1A 26 5026 uint RWE W P1 W P1 Subroutine Step 1 to 150 Wait For Process 1 Enter a value that must be satisfied which is specifi...

Страница 135: ...hether process value must be Less Than or Greater Than the value of Wait for Process to satisfy the wait for condition oFF Off 62 L t Less Than 1436 g t Greater Than 1435 Off 30496 offset 86 0x69 105...

Страница 136: ...y 1565 Every Day 30508 offset 86 0x69 105 1 to 150 0x23 35 5035 uint RWE gSE1 gSE1 Subroutine Step 1 to 150 Guaranteed Soak Enable 1 Select if profile should pause while process 1 deviates from devia...

Страница 137: ...utine Step 1 to 150 Event 4 Select whether output programmed as Pro file Event Out D is on unchanged or off dur ing this step Ucgd Unchanged 1557 oFF Off 62 on On 63 Un changed 30472 offset 86 0x69 10...

Страница 138: ...outine Step 1 to 150 Event 8 Select whether output programmed as Pro file Event Out H is on unchanged or off dur ing this step Ucgd Unchanged 1557 oFF Off 62 on On 63 Un changed 30480 offset 86 0x69 1...

Страница 139: ...Target Set Point Loop 4 hoUr Hours Min Minutes SEC Seconds gSE1 Guaranteed Soak Enable 1 gSE2 Guaranteed Soak Enable 2 gSE3 Guaranteed Soak Enable 3 gSE4 Guaranteed Soak Enable 4 Ent1 Event 1 Ent2 Ev...

Страница 140: ...ore proceed ing to the next step Used to have the profile execute steps everyday or only weekdays The state of up to 8 event out puts may be set or maintained hoUr Hours Min Minutes SEC Seconds dow Da...

Страница 141: ...of up to 8 event outputs may be set or maintained This step type not available in subroutine SS Subroutine Step SC Subroutine Count Ent1 Event 1 Ent2 Event 2 Ent3 Event 3 Ent4 Event 4 Ent5 Event 5 Ent...

Страница 142: ...lope Note Some of these menus and parameters may not appear depending on the controller s options See model number information in the Appendix for more information If there is only one instance of a m...

Страница 143: ...aranteed Soak Devia tion 1 Value gSd2 Guaranteed Soak Devia tion 2 Value P ACr Profile Action Request P Str Profile Start idLE Idle Set Point t tUn TRU TUNE Enable r rt Ramp Rate C hy Cool Hysteresis...

Страница 144: ...int RWE pas e LoC P Security Setting Password Enable Turn Password En able ON if a Password access feature is desired This is in ad dition to Read Lock or Write Security off Off on On Off rLoC rLoC Se...

Страница 145: ...vel Determines user level menu visibility when Password is enabled See Features section under Password Secu rity This setting is in addition to Read Lock and Write Security Consider using only Locked...

Страница 146: ...If Rolling Password is OFF a fixed number will be displayed The Public Key is only re quired if the assigned Password is unknown Provide the key to the OEM or technical sup port to gain access Custom...

Страница 147: ...elec trical value for this input in the units cor responding to the Sen sor Type Setup Page Analog Input Menu setting 3 4e38 to 3 4e38 400 offset 90 0x68 104 1 to 4 0x15 21 4021 float R ELi o ELi o C...

Страница 148: ...ite ELo S ELo S Calibration Menu 1 3 5 7 Electrical Output Slope Adjust this value to calibrate the slope of the output value 1 999 000 to 9 999 000 1 0 850 1 896 3 940 5 986 7 0x76 118 1 to 4 6 18006...

Страница 149: ...iguration 153 Auto closed loop and Manual open loop Control 153 On Off Control 154 Proportional P Control 155 Proportional plus Integral PI Control 155 Proportional Integral and Derivative PID Control...

Страница 150: ...n 169 Control Function 171 Counter Function 173 Custom Function 173 Diagnostic Function 173 Digital Input Output Function 174 Global Function 174 Limit Function 175 Linearization Function 175 Logic Fu...

Страница 151: ...or cooling PID parameter settings based on the sys tems response Autotuning can be enabled whether or not TRU TUNE is enabled The PID settings generated by the autotune will be used until the au totun...

Страница 152: ...for the PID parameters Then the loop automatically switches to the adaptive mode which fine tunes the PID parameters Once the Process Value has been at set point for a suitable period about 30 minutes...

Страница 153: ...analog input you will need to provide a source of two electrical signals or resistance values near the extremes of the range that the application is likely to utilize See recommended values below Sen...

Страница 154: ...ut sensor of choice Turn sensor backup on or off via the Setup Page Process Value Menu Source Function A must select a backup sensor from the same module zone where Source Function B through D can sel...

Страница 155: ...Off the output will match the Source A value plus offset There are 10 data points used to compen sate for differences between the source value read input point and the desired value output point Mult...

Страница 156: ...tput Curve A nonlinear output curve may improve performance when the response of the output device is nonlinear If a cool output uses one of the nonlinear curves a PID calculation yields a lower actua...

Страница 157: ...loop control If the controller was in manual mode when the error occurred the controller will remain in open loop control The Manual Control Indicator Light is on when the controller is operating in...

Страница 158: ...eset control When the system settles down the integral value is tuned to bring the temperature or process value closer to the set point Integral determines the speed of the correction but this may inc...

Страница 159: ...relay SSR or silicon controlled rectifier SCR power controller Do not use a variable time base output for control ling electromechanical relays mercury displacement relays inductive loads or heaters w...

Страница 160: ...p is determined by the outer loop power level The inner loop input any input monitors the energy source heating and cooling which is compared to the inner loop set point generated by the outer loop Th...

Страница 161: ...the alarm condition is over Configure alarm outputs in the Setup Page before setting alarm set points Alarms do not have to be assigned to an output Alarms can be monitored and controlled through the...

Страница 162: ...display 2 Use the Up and Down keys to scroll through possible responses such as Clear CLr or Silence SiL 3 Push the Advance or Infinity key to execute the action Without an RUI silencing aa alarm can...

Страница 163: ...sing Lockout to Hide Pages and Menus If unintentional changes to parameter settings might raise safety concerns or lead to downtime your can use the lockout feature to make them more secure These sett...

Страница 164: ...ons Page security levels Change Lock Opera tions Page LoC o to 3 and Lock Profiling Page LoC P to 2 If Set Lockout Security SLoC is set to 2 or higher and the Read Lockout Security rLoC is set to 2 th...

Страница 165: ...the the Rolling Password is off push the Ad vance key one more time where the Password pass prompt will be displayed Proceed to either step 7a or 8a Pushing the Up or Down arrow keys enter either the...

Страница 166: ...ses 40 41 When the Modbus address of a target parameter is stored in an Assembly Definition Address its cor responding working address will return that parame ter s actual value If it s a writable par...

Страница 167: ...ow If the PC is already physically connected to the RMC module click the next button to go on line Note When establishing communications from PC to the RMC module an interface converter will be requir...

Страница 168: ...visible Simply slide the scroll bar up or down to display the menu and parameter of choice As an alternative clicking on the negative symbol next to Setup will collapse the Setup Menu where the Op er...

Страница 169: ...reason someone inadvertently changed a set ting without understanding the impact it would be easy and perhaps faster to download a saved configu ration back to the control versus trying to figure out...

Страница 170: ...ilence Request 0 a st Alarm State Startup None Blocked Alarm Low Alarm High Error Function Block Descriptions Each of the next several pages graphically shows each of the RMC function blocks Note that...

Страница 171: ...d Alarm State Error Alarm Source Alarm Source Instance Alarm Source Zone Alarm Source Error Control Loop Analog Input Function Note This Function configures and connects physical inputs to internal fu...

Страница 172: ...read can indicate any of the follow ing None Open Shorted Measurement Error Bad Cal Data Ambient Error RTD Error Fail Math Er ror Not Sourced Stale Tolerance is expressed in the same units as Source...

Страница 173: ...A Source Zone A Source Error A Source Function B Source Instance B Source Zone B Source Error B Compare Equal To Compare Greater or Equal Compare Less or Equal A not equal B Output Value ON A B Outpu...

Страница 174: ...e Set Point 50 to 200 AUt Autotune No Yes C SP Closed Loop Set Point 1 999 000 to 9 999 000 id S Idle Set Point 1 999 000 to 9 999 000 h Pb Heat Proportional Band 0 001 to 9 999 000 h hy Heat Hysteres...

Страница 175: ...orithm Cool Algorithm TRU TUNE Enable Autotune Aggressiveness TRU TUNE Band TRU TUNE Gain Cool Output Curve Autotune Set Point Autotune Closed Loop Set Point Idle Set Point Heat Proportional Band Cool...

Страница 176: ...on A Source Instance A Source Zone A Source Error A Source Function B Source Instance B Source Zone B Source Error B LoadValue TargetValue Latching Count Ctr Counter Menu SEt Operation Page Ctr Counte...

Страница 177: ...ool Power Heat Power Compare Counter Digital I O Profile Event Out A to H Function Key Logic Linearization Math Process Value Special Function Output 1 to 4 Timer Variable Digital Input Value On Off A...

Страница 178: ...nt 4 Output Point 5 Output Point 6 Output Point 7 Output Point 8 Output Point 9 Output Point 10 Offset Input Point 2 Input Point 3 Input Point 4 Input Point 5 Input Point 6 Input Point 7 Input Point 8...

Страница 179: ...Point 3 Input Point 4 Input Point 5 Input Point 6 Input Point 7 Input Point 8 Input Point 9 Input Point 10 WHILE Source A Input Point n n n 1 FROM n 2 UNTIL n is largest valid value Output Value Outp...

Страница 180: ...1 to 4 Timer Variable SFn f Source Function F None Alarm Compare Counter Digital I O Profile Event Out A to H Function Key Limit Logic Special Function Output 1 to 4 Timer Variable SFn g Source Functi...

Страница 181: ...ce Instance H Source Zone H Source Error H Function Error Handling Source Value A Source Value B Source Value C Logic Not Equal If A B C D E F G H then ON Error Source Value D Source Value F Source Va...

Страница 182: ...Source Zone H Source Error H Function Error Handling Source Value A Source Value B Source Value C Logic Off Output Value Off Error Source Value D Source Value F Source Value E Source Value H Output V...

Страница 183: ...Maximum Square Root Sample and Hold Pressure to Altitude Dewpoint sfn b Source Function B None Analog Input Current Cool Power Heat Power Power Linearization Math Process Value Set Point Closed Set Po...

Страница 184: ...Source Error D Source Function E Source Instance E Source Zone E Source Error E Source Value A Source Value B Source Value C Source Value D Source Value E Output Value Error Math Switch Over Range Low...

Страница 185: ...ce Zone E Source Error E Source Value A Source Value B Source Value C Source Value D Source Value E Output Value Error Math Multiply Range Low Range High Pressure Units Altitude Units Scale Low Scale...

Страница 186: ...e High Function Filter Offset Filter Output Value Filter Sqr Root A Offset Display units follows Source A Source Function A Source Instance A Source Zone A Source Error A Source Function B Source Inst...

Страница 187: ...B Source Value C Source Value D Source Value E Output Value Error Output Function This function configures and connects physical outputs to internal functions Note Digital Outputs not included on thes...

Страница 188: ...ol Output High Power Scale Output Function Output Function Instance Output Source Zone Output Source Error Output Function Output Function Instance Output Source Zone Output Source Error Output Value...

Страница 189: ...8 Profile Action Request Profile Start Ramping Type Profile Type Guaranteed Soak Deviation 1 to 4 Guaranteed Soak Enable Source Function A Source Instance A Source Zone A Source Error A Source Functi...

Страница 190: ...Set Point Closed Set Point Open Variable sfn g Source Function G Wait Analog 3 None Analog Input Current Cool Power Heat Power Power Linearization Math Process Value Set Point Closed Set Point Open Va...

Страница 191: ...rget Set Point Loop 1 to 4 1 999 000 to 9 999 000 hoUr Hours 0 to 99 Min Minutes 0 to 59 SEC Seconds 0 to 59 rAtE Rate 0 to 9 999 000 P E1 P E2 P E3 P E4 Step Wait For Process Enable 1 to 4 Off Greate...

Страница 192: ...r E Source Function F Source Instance F Source Zone F Source Error F Source Function G Source Instance G Source Zone G Source Error G Source Function H Source Instance H Source Zone H Source Error H C...

Страница 193: ...e Instance F Source Zone F Source Error F Source Function G Source Instance G Source Zone G Source Error G Source Function H Source Instance H Source Zone H Source Error H Current Step Current Subrout...

Страница 194: ...rror F Source Function G Source Instance G Source Zone G Source Error G Source Function H Source Instance H Source Zone H Source Error H Current Step Current Subroutine Step Step Type Target Set Point...

Страница 195: ...E Source Zone E Source Error E Source Function F Source Instance F Source Zone F Source Error F Source Function G Source Instance G Source Zone G Source Error G Source Function H Source Instance H Sou...

Страница 196: ...E Source Function F Source Instance F Source Zone F Source Error F Source Function G Source Instance G Source Zone G Source Error G Source Function H Source Instance H Source Zone H Source Error H Cu...

Страница 197: ...Source Zone G Source Error G Source Function H Source Instance H Source Zone H Source Error H Current Step Current Subroutine Step Step Type Target Set Point Loop 1 to 4 Active Set Point Loop 1 to 4...

Страница 198: ...Error F Source Function G Source Instance G Source Zone G Source Error G Source Function H Source Instance H Source Zone H Source Error H Current Step Current Subroutine Step Step Type Target Set Poi...

Страница 199: ...r F Source Function G Source Instance G Source Zone G Source Error G Source Function H Source Instance H Source Zone H Source Error H Current Step Current Subroutine Step Step Type Target Set Point Lo...

Страница 200: ...nstance G Source Zone G Source Error G Source Function H Source Instance H Source Zone H Source Error H Current Step Current Subroutine Step Step Type Target Set Point Loop 1 to 4 Active Set Point Loo...

Страница 201: ...e Function H Source Instance H Source Zone H Source Error H Current Step Current Subroutine Step Step Type Target Set Point Loop 1 to 4 Active Set Point Loop 1 to 4 Step Time Remaining Jump Count Rema...

Страница 202: ...Barometric Pressure Cross Over Point Cross Over Band Function Filter Offset Output Value Error S2 A Source Zone A 0 to 16 S2 C Source Zone C 0 to 16 S2 E Source Zone E 0 to 16 S2 b Source Zone B 0 to...

Страница 203: ...nd Function Function Filter Filter Offset Offset Process Value Sensor Backup Process Value Crossover Source Function A Source Instance A Source Error A Source Function B Source Instance B Source Zone...

Страница 204: ...ry Bulb and Source B is the Wet Bulb Note Wet Dry bulb temperatures are in degrees F and pressures are in PSI Output Value is relative humidity Useful temperature range is 10 to 350F Process Value Swi...

Страница 205: ...mperature source else follow Source A Output Value Filter A B Offset Display units follow Source A plus relative Source B Process Value Multiply Process Value Minimum Output Value Filter A B C D Offse...

Страница 206: ...e This calculation is effective over the temperature range of 75F to 350F Process Value Square Root Process Value Pressure to Altitude Output Value Filter Convert Source A in Pressure to Altitude Offs...

Страница 207: ...Output Overview Instances 4 per RMC S2 A Source Zone A 0 to 16 S2 b Source Zone B 0 to 16 Pon A Power On Level 1 100 0 to 100 0 Pon b Power On Level 2 100 0 to 100 0 PoF A Power Off Level 1 100 0 to 1...

Страница 208: ...Instance B Source Zone B Source Error B Source Function B Source Instance B Source Zone B Source Error B Power On Level 1 Power On Level 1 Power On Level 2 Power On Level 2 Power Off Level 1 Power Of...

Страница 209: ...B Off On o u Output Value Off On E t Elapsed Time 0 0 to 9 999 000 seconds ti Time 0 to 9 999 seconds tMr Timer Menu SEt Setup Page SAS A Source Active State A Timer Run High rising Low falling SAS b...

Страница 210: ...se with active state falling edge 0 0 0 0 Time ti Time ti off off off off low low high high on on on on Timing Diagram of On Pulse with active state rising edge Timer On Pulse Function SourceActive St...

Страница 211: ...e B Source Zone B Source Error B Time Active Level Output Value Error Source Value A Source Value B Elapsed Time A delay timer is used to cause a delaying action The delay can be made to happen on eit...

Страница 212: ...nstance B Source Zone B Source Error B Time Active Level Output Value Error Source Value A Source Value B Elapsed Time The One Shot timer functions like a simple oven timer The time value gets set by...

Страница 213: ...ce Zone B Source Error B Time Active Level Output Value Error Source Value A Source Value B Elapsed Time A retentive timer is used to keep track of how much time something has been in a particular sta...

Страница 214: ...e as one input to a compare function The other input to the compare function would determine the output value based on the user s supplied value Variable Overview Instances 8 per RMC Data Type Digital...

Страница 215: ...212 213 54 55 214 215 56 57 216 217 58 59 218 219 60 61 220 221 62 63 222 223 64 65 224 225 66 67 226 227 68 69 228 229 70 71 230 231 72 73 232 233 74 75 234 235 76 77 236 237 78 79 238 239 80 81 240...

Страница 216: ...Point Value of Pointer 18 Pointer 19 0 1 Alarm 3 Low Set Point Value of Pointer 19 Pointer 20 0 1 Alarm 4 Low Set Point Value of Pointer 20 Pointer 21 0 1 Analog Input 1 Registers 80 81 Registers 240...

Страница 217: ...Right angle and front screw type terminal blocks slots A B D E Input power and controller output terminals touch safe re movable 12 to 30 AWG Wire strip length 7 6 mm 0 30 in Torque 0 8 Nm 7 0 lb in...

Страница 218: ...ac signal user programmable range Displayed operating range and resolution can be scaled and are user programmable Output Hardware Switched dc Max 32V dc open circuit Max current 30mA per single outpu...

Страница 219: ...Actions events 8 total Alarms 8 total Control Loop 4 total Compare 4 total Off greater than less than equal not equal greater than or equal less than or equal Counters 4 total Counts up or down loads...

Страница 220: ...chanical relay options XX Custom Locked Firmware A Standard bus 1 Standard bus and Modbus RTU 485 A Right angle screw connector standard F Front screw connector Output 7 Output 8 A None None B None Me...

Страница 221: ...Fi Digital Output Function Instance 66 Fi Output Function Instance 77 78 79 FiL Filter 60 Fn Output Function 77 79 gLbL Global Menu 111 gSd Guaranteed Soak Deviation 112 gSE Guaranteed Soak Enable 111...

Страница 222: ...59 Assembly Definition Addresses 163 Assembly Working Addresses 163 auto closed loop control 153 Autotune 148 Autotune Aggressiveness 73 Autotune Request 41 Autotune Set Point 41 73 148 autotuning 14...

Страница 223: ...128 Jump Count Remaining 55 Jump Loop 138 Jump Step 128 K L Latching 82 Limit Menu 40 69 Linearization 59 Linearization Menu 45 84 line voltage power 214 Locked Access Level 142 Lock Operations Page 1...

Страница 224: ...8 155 Time Integral 42 72 148 155 Timer Function 206 Timer Menu 46 88 TRU TUNE Band 72 149 TRU TUNE Enable 72 149 TRU TUNE Gain 72 149 tuning the PID parameters 148 Type 80 U Unused Step 136 USB conve...

Страница 225: ...ng EN 61000 4 2 1996 A1 A2 2001 Electrostatic Discharge Immunity EN 61000 4 3 2006 Radiated Field Immunity EN 61000 4 4 2004 Electrical Fast Transient Burst Immunity EN 61000 4 5 2006 Surge Immunity E...

Страница 226: ...he United Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Pacific Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singapore 139965 Tel 65 6773 9488 Fax 65 6778 0323 Email info watlow...

Отзывы: