Watlow EZ-ZONE
®
RMC Module
•
41
•
Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`h;Pr]
[ h.Pr]
Monitor (1 to 4)
Heat Power
View the current heat
output level.
0.0 to 100.0%
- - - -
2244
[offset 70]
0x97 (151)
1 to 4
0xD (13)
- - - -
8011
float
R
[`C;Pr]
[ C.Pr]
Monitor (1 to 4)
Cool Power
View the current cool
output level.
-100.0 to 0.0%
- - - -
2246
[offset 70]
0x97 (151)
1 to 4
0xE (14)
- - - -
8014
float
R
[`C;SP]
[ C.SP]
Monitor (1 to 4)
Closed Loop Working
Set Point
View the set point cur-
rently in effect.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
- - - -
0x6B (107)
1 to 4
7
- - - -
8029
float
R
[`Pu;A]
[ Pv.A]
Monitor (1 to 4)
Process Value Active
View the current filtered
process value using the
control input.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
- - - -
0x68 (104)
1 to 4
0x16 (22)
- - - -
8031
float
R
[Loop]
[oPEr]
Loop Menu
[`r;En]
[ r.En]
Control Loop (1 to 4)
Remote Enable
Enable this loop to
switch control to the
remote set point.
[``no]
No (59)
[`YES]
Yes (106)
No
2540
[offset 80]
0x6B
(107)
1 to 4
0x15 (21)
48
7021
uint
RWES
[`C;M]
[ C.M]
Control Loop (1 to 4)
Control Mode
Select the method that
this loop will use to
control.
[`off]
Off (62)
[AUto]
Auto (10)
[MAn]
Manual (54)
Auto
2220
[offset 70]
0x97
(151)
1 to 4
1
63
8001
uint
RWES
[A;tSP]
[A.tSP}
Control Loop (1 to 4)
Autotune Set Point
Set the set point that
the autotune will use,
as a percentage of the
current set point.
50.0 to 200.0%
90.0
2258
[offset 70]
0x97
(151)
1 to 4
0x14 (20)
- - - -
8025
float
RWES
[`AUt]
[ AUt]
Control Loop (1 to 4)
Autotune Request
Start an autotune. While
the autotune is active,
the Home Page will
display
[Attn]
[tUn1]
.
When the autotune is
complete, the message
will clear automatically.
[``no]
No (59)
[`YES]
Yes (106)
No
2260
[offset 70]
0x97
(151)
1 to 4
0x15 (21)
64
8026
uint
RW
[`C;SP]
[ C.SP]
Control Loop (1 to 4)
Closed Loop Set Point
Set the set point that
the controller will auto-
matically control to.
Low Set Point to High Set
Point (Setup Page)
75.0°F
or
units
24.0°C
2500
[offset 80]
0x6B
(107)
1 to 4
1
49
7001
float
RWES
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set