![Watlow EZ-ZONE RMC Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/watlow/ez-zone-rmc/ez-zone-rmc_user-manual_3748884051.webp)
Watlow EZ-ZONE
®
RMC Module
•
48
•
Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`LgC]
[oPEr]
Logic Menu
[`Su;A]
[ Su.A]
Logic (1 to 4)
Source Value A
View the value of
Source A.
[`off]
Off (62)
[``on]
On (63)
- - - -
3728
[offset 80]
0x7F
(127)
1 to 4
0x19 (25)
- - - -
27025
uint
R
[`Su;b]
[ Su.b]
Logic (1 to 4)
Source Value B
View the value of
Source B.
[`off]
Off (62)
[``on]
On (63)
- - - -
3730
[offset 80]
0x7F
(127)
1 to 4
0x1A (26)
- - - -
27026
uint
R
[`Su;C]
[ Su.C]
Logic (1 to 4)
Source Value C
View the value of
Source C.
[`off]
Off (62)
[``on]
On (63)
- - - -
3732
[offset 80]
0x7F
(127)
1 to 4
0x1B (27)
- - - -
27027
uint
R
[`Su;d]
[ Su.d]
Logic (1 to 4)
Source Value D
View the value of
Source D.
[`off]
Off (62)
[``on]
On (63)
- - - -
3734
[offset 80]
0x7F
(127)
1 to 4
0x1C (28)
- - - -
27028
uint
R
[`Su;E]
[ Su.E]
Logic (1 to 4)
Source Value E
View the value of
Source E.
[`off]
Off (62)
[``on]
On (63)
- - - -
3736
[offset 80]
0x7F
(127)
1 to 4
0x1D (29)
- - - -
27029
uint
R
[`Su;F]
[ Su.F]
Logic (1 to 4)
Source Value F
View the value of
Source F.
[`off]
Off (62)
[``on]
On (63)
- - - -
3738
[offset 80]
0x7F
(127)
1 to 4
0x1E (30)
- - - -
27030
uint
R
[`Su;g]
[ Su.g]
Logic (1 to 4)
Value Source G
View the value of
Source G.
[`off]
Off (62)
[``on]
On (63)
- - - -
3740
[offset 80]
0x7F
(127)
1 to 4
0x1F (31)
- - - -
27031
uint
R
[`Su;h]
[ Su.h]
Logic (1 to 4)
Source Value H
View the value of
Source H.
[`off]
Off (62)
[``on]
On (63)
- - - -
3742
[offset 80]
0x7F
(127)
1 to 4
0x20 (32)
- - - -
27032
uint
R
[``o;u]
[ o.v]
Logic (1 to 4)
Output Value
View the value of this
function's output.
[`off]
Off (62)
[``on]
On (63)
- - - -
3746
[offset 80]
7F (127)
1 to 4
0x22 (34)
- - - -
27034
uint
R
No Dis-
play
Logic (1 to 4)
Error
Read reported cause for
logic error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
- - - -
3750
[offset 80]
0x7F
(127)
1 to 4
0x24 (36)
- - - -
27036
uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set