Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`A;hi]
[ A.hi]
Alarm (1 to 8)
High Set Point
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process
- set the pro-
cess value that will
trigger a high alarm.
deviation
- set the
span of units from the
closed loop set point
that will trigger a low
alarm. A negative set
point represents a
value below closed loop
set point. A positive
set point represents a
value above closed loop
set point.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
300.0°F
or
units
150.0°C
1740
[offset 60]
0x6D
(109)
1 to 8
1
19
9001
float
RWES
[a;Clr]
[A.CLr]
Alarm (1 to 8)
Alarm Clear Request
Write to this register to
clear an alarm
0
- - - -
1764
[offset 60]
0x6D
(109)
1 to 8
0xD (13)
32
9013
uint
W
[A;sir]
[A.Sir]
Alarm (1 to 8)
Alarm Silence Re-
quest
Write to this register to
silence an alarm
0
- - - -
1766
[offset 60]
0x6D
(109)
1 to 8
0xE (14)
33
9014
uint
W
[`a;st]
[ A.St]
Alarm (1 to 8)
Alarm State
Current state of alarm
Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)
- - - -
1756
[offset 60]
0x6D
(109)
1 to 8
9
- - - -
9009
uint
R
No Dis-
play
Alarm (1 to 8)
Alarm Clearable
Read to see if alarm
can be cleared.
[``no]
No (59)
[`YES]
Yes (106)
- - - -
1762
[offset 60]
0x6D
(109)
1 to 8
0xC (12)
- - - -
9012
uint
R
No Dis-
play
Alarm (1 to 8)
Silenced
Read to see if alarm is
active but has been si-
lenced by Alarm Silence
Request.
Yes (106)
No (59)
- - - -
1760
[offset 60]
0x6D
(109)
1 to 4
0x0B (11)
- - - -
9011
uint
R
No Dis-
play
Alarm (1 to 8)
Latched
Read to see if alarm is
currently latched.
Yes (106)
No (59)
- - - -
1758
[offset 60]
0x6D
(109)
1 to 4
0x0A (10)
- - - -
9010
uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set