Watlow EZ-ZONE
®
RMC Module
•
67
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`o;Ct]
[ o.Ct]
Digital Output (7 to 12)
Control
Set the output control
type. This parameter
is only used with PID
control, but can be set
anytime.
[`Ftb]
Fixed Time Base (34)
[`utb]
Variable Time Base
(103)
Fixed
Time
Base
1022
[offset 30]
0x6A
(106)
7 to 0x0C
(12)
2
85
6002
uint
RWES
[`o;tb]
[ o.tb]
Digital Output (7 to 12)
Time Base
Set the time base for
fixed-time-base control.
0.1 to 60.0 seconds
1.0
1024
[offset 30]
0x6A
(106)
7 to 0x0C
(12)
3
86
6003
float
RWES
[`o;Lo]
[ o.Lo]
Digital Output (7 to 12)
Low Power Scale
The power output will
never be less than the
value specified and will
represent the value at
which output scaling
begins.
0.0 to 100.0
0.0
1036
[offset 30]
0x6A
(106)
7 to 0x0C
(12)
9
87
6009
float
RWES
[`o;hi]
[ o.hi]
Digital Output (7 to 12)
High Power Scale
The power output will
never be greater than
the value specified and
will represent the value
at which output scaling
stops.
0.0 to 100.0
100.0
1038
[offset 30]
0x6A
(106)
7 to 0x0C
(12)
A (10)
88
6010
float
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set