Chapter 2 Install and Wire
Wiring a Serial EIA-485 Network
Do not route network wires with power wires. Con-
nect network wires in daisy-chain fashion when con-
necting multiple devices in a network. A termina-
tion resistor may be required. Place a 120 Ω resistor
across T+/R+ and T-/R- of the last controller on a
network. Only one protocol per port is available at a
time: either Modbus RTU or Standard Bus.
Note:
Termination resistors when used, require a termina-
tion resistor at both ends of the network.