Watlow EZ-ZONE
®
RMC Module
•
104
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`S2;C]
[ SZ.C]
Math (1 to 8)
Source Zone C
Set the zone of the func-
tion selected above.
0 to 16
0
2864
[offset 70]
0x7D
(125)
1 to 8
0xD (13)
- - - -
25013
uint
RWES
[SFn;D]
[SFn.d]
Math (1 to 8)
Source Function D
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop (73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed, Con-
trol Loop (242)
[`SP;o]
Set Point Open, Control
Loop (243)
[`uAr]
Variable (245)
None
2846
[offset 70]
0x7D
(125)
1 to 8
4
- - - -
25004
uint
RWES
[`si;d]
[ Si.d]
Math (1 to 8)
Source Instance D
Set the instance of the
function selected above.
1 to 24
1
2856
[offset 70]
0x7D
(125)
1 to 8
9
- - - -
25009
uint
RWES
[`S2;D]
[ SZ.d]
Math (1 to 8)
Source Zone D
Set the zone of the func-
tion selected above.
0 to 16
0
2866
[offset 70]
0x7D
(125)
1 to 8
0xE (14)
- - - -
25014
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set