Watlow EZ-ZONE
®
RMC Module
•
106
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[Unit]
[Unit]
Math (1 to 8)
Units
Set units for Source.
[`Src]
Source (1539)
[nonE]
None (61)
[`A;tP]
Absolute Temperature
(1540)
[`r;tp]
Relative Temperature
(1541)
[PWr]
Power (73)
[`pro]
Process (75)
[``rh]
Relative Humidty (1538)
Source
2902
[offset 70]
0x7D
(125)
1 to 8
0x20 (32)
- - - -
25032
uint
RWES
[`r;Lo]
[ r.Lo]
Math (1 to 8)
Range Low
If Math function is set to
Process Scale, this will
output Source A Scale
Low value to Range Low
setting.
-1,999.000 to 9,999.000
0.0
2890
[offset 70]
0x7D
(125)
1 to 8
0x1A (26)
131
25026
float
RWES
[`r;hi]
[ r.hi]
Math (1 to 8)
Range High
If Math function is set to
Process Scale, this will
output Source A Scale
High value to Range
High setting.
-1,999.000 to 9,999.000
1.0
2892
[offset 70]
0x7D
(125)
1 to 8
0x1B (27)
132
25027
float
RWES
[p;unt]
[P.unt]
Math (1 to 8)
Pressure Units
If Math function is set
for Pressure to Altitude
units, set units of mea-
sure for conversion.
[`psi]
Pressure Units (1671)
[pasc]
Pascal (1674)
[atm]
Atmosphere (1675)
[mbr]
mbar (1672)
[torr]
Torr (1673)
Pressure
Units
2898
[offset 70]
0x7D
(125)
1 to 8
0x1E (30)
- - - -
25030
uint
RWES
[a;unt]
[A.unt]
Math (1 to 8)
Altitude Units
If Math function is set
for Pressure to Altitude
units, set units of mea-
sure for conversion.
[`Hft]
Kilofeet (1671)
[``ft]
Feet (1674)
Kilofeet
2900
[offset 70]
0x7D
(125)
1 to 8
0x1F (31)
- - - -
25031
uint
RWES
[`FiL]
[ FiL]
Math (1 to 8)
Filter
Filtering smooths out
the output signal of this
function block. Increase
the time to increase fil-
tering.
0.0 to 60.0 seconds
0.0
2894
[offset 70]
0x7D
(125)
1 to 8
0x1C (28)
- - - -
25028
float
RWES
`SoF]
[`Set]
Special Output Function Menu
[``Fn]
[ Fn]
Special Output (1 to 4)
Function
Set the function to
match the device it will
operate.
[`oFF]
Off (62)
[`Co;C]
Compressor Control
(1506)
[`uA;C]
Motorized Valve (1508)
[`SE;C]
Sequencer (1507)
Off
4976
[offset 80]
0x87 (135)
1 to 4
9
181
35009
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set