Watlow EZ-ZONE
®
RMC Module
•
132
•
Chapter 5 Profiling Page
RMC Module •
Profile Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data Type
& Read/
Write
[`P;E3]
[P.E3]
Subroutine Step (1 to
150)
Step Wait For Pro-
cess Enable 3
If step type is Wait
for Process or Event,
select whether process
value must be Less
Than or Greater Than
the value of Wait for
Process to satisfy the
wait-for condition.
[`oFF]
Off (62)
[``L;t]
Less Than (1436)
[``g;t]
Greater Than
(1435)
Off
30494
[offset 86]
0x69
(105)
1 to (150)
0x1C (28)
- - - -
5028
uint
RWE
[W;P3]
[W.P3]
Subroutine Step (1 to
150)
Wait For Process 3
Enter a value that
must be satisfied
which is specified by
Source G in Profile
Setup.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
30502
[offset 86]
0x69
(105)
1 to (250)
0x20 (32)
- - - -
5032
float
RWE
[`P;E4]
[P.E4]
Subroutine Step (1 to
150)
Step Wait For Pro-
cess Enable 4
If step type is Wait
for Process or Event,
select whether process
value must be Less
Than or Greater Than
the value of Wait for
Process to satisfy the
wait-for condition.
[`oFF]
Off (62)
[``L;t]
Less Than (1436)
[``g;t]
Greater Than
(1435)
Off
30496
[offset 86]
0x69
(105)
1 to (250)
0x1D
(29)
- - - -
5029
uint
RWE
[W;P4]
[W.P4]
Subroutine Step (1 to
150)
Wait For Process 4
Enter a value that
must be satisfied
which is specified by
Source H in Profile
Setup.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
30504
[offset 86]
0x69
(105)
1 to (250)
0x21 (33)
- - - -
5033
float
RWE
[WE;1]
[WE.1]
Subroutine Step (1 to
150)
Wait Event 1
Enter a state that
must be satisfied
which is specified by
Source A in Profile
Setup.
[nonE]
None (61)
[``on]
On (63)
[`oFF]
Off (62)
None
30482
[offset 86]
0x69
(105)
1 to (150)
0x16 (22)
- - - -
5022
uint
RWE
[WE;2]
[WE.2]
Subroutine Step (1 to
150)
Wait Event 2
Enter a state that
must be satisfied
which is specified by
Source B in Profile
Setup.
[nonE]
None (61)
[``on]
On (63)
[`oFF]
Off (62)
None
30484
[offset 86]
0x69
(105)
1 to (150)
0x17 (23)
- - - -
5023
uint
RWE
Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EEPROM
S: User Set