765-4501/0100-0000
Commissioning
96
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
1. Select the port to which the IO-Link device is connected from the menu on the left.
2. Open the
IOL
tab.
ð
The
IOL
tab appears.
Read Access
Figure 17: Ports X01 ... X08 – Read Access to IO-Link Device
To read data from the connected IO-Link device, proceed as follows:
1. On the
IOL
tab, enter the index of the connected IO-Link device you want to access
into the
Index
field as a hexadecimal value.
2. On the
IOL
tab, enter the subindex of the connected IO-Link device you want to ac-
cess into the
Subindex
field as a hexadecimal value; the default setting is 00
3. Click the
[Read]
button.
ð
The read operation is performed. An entry is written to the history at the bottom of the
tab and logged there with the current time.
If the operation was successful, the text
Read ok:
and the result appear in the history.
The entries in the history then have the following structure:
Time – Index:Subindex – Read ok: <Result>