765-4501/0100-0000
Planning
Product manual | Version: 1.1.0
65
8PORT IOL-A FLD EI DC 24V 2.0A
Table 47: Module Parameters
No.
Parametername
Value Range
Default
Description
90
DIO process data
layout
0: Port-based
0
Order of the process data of the digital in-
puts and digital outputs:
Bit 0 = port X01 pin 4,
Bit 1 = port X01 pin 2,
bit 2 = port X02 pin 4,
bit 3 = port X02 pin 2,
...
1: Pin-based
Order of the process data of the digital in-
puts and digital outputs:
Bit 0 = port X01 pin 4,
Bit 1 = port X02 pin 4,
Bit 2 = port X03 pin 4,
Bit 3 = port X04 pin 4,
...
Bit 8 = port X01 pin 2,
Bit 9 = port X02 pin 2,
...
91
DO substitute mode
0: Set to low
0
Set all digital outputs to low level in the
event of error
1: Use substitute val-
ues
Set digital outputs to a pre-defined substi-
tute value in the event of error.
If this setting is used, the value of the “DO
substitute value” parameter determines the
substitute value.
2: Hold last state
Hold digital outputs at their last value in the
event of error
92
DO substitute values 0 ... 65535
0
Substitute value for the digital outputs if the
“Use substitute values” setting is used. The
input depends on the “DIO process data
layout” parameter.
Use a binary-to-decimal converter to calcu-
late this value.
93
Disable force mode
0: Enable force
mode
0
The “Forcing” operating mode may be
used.
1: Disable force
mode
The “Forcing” operating mode must not be
used.
94
Disable bluetooth
0: Enable bluetooth
0
The Bluetooth
®
interface can be enabled by
an optical signal of a mobile device and in
connection with the WAGO I/O Field app.
1: Disable bluetooth
The Bluetooth
®
interface cannot be enabled
by an optical signal of a mobile device and
in connection with the WAGO I/O Field app.
95
Bluetooth timeout
6 ... 59 [s]
30
Switch-off time of the Bluetooth interface if
not used.
A new Bluetooth connection can be estab-
lished by an optical signal after the Blue-
tooth interface is enabled again.
The unit for the switch-off time is seconds.
Entering 0 is not allowed, since the Blue-
tooth interface must always switch off after
the switch-off time elapses.
96
Reserved
0
0
–