765-4501/0100-0000
Commissioning
92
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
10.3.1.4.1 Configure Ports
Figure 16:
Port XX
Menu Item,
Configuration
Tab
The
Configuration
tab is used to display and modify the following port settings for the se-
lected port of the device:
Table 58: Port Configuration Settings for IO-Link Devices
Name
Type
Description
Port mode (pin 4)
Drop-down menu
Port operating mode (configuration of pin 4)
Digital input signal filter
(pin 4)
Drop-down menu
Filter time for digital input signals on pin 4 (only for
“Port mode (pin 4)” on digital input)
IQ behavior (pin 2)
Drop-down menu
IQ behavior of the port (configuration of pin 2)
Validation and backup
Drop-down menu
Validation and Backup Settings for Device Check
When Replacing Devices
PortCycleTime
Input field
Expected cycle time of the port
VendorID
Input field
Expected manufacturer ID of the connected device
DeviceID
Input field
Expected device ID of the connected device
The
Validation and Backup
,
PortCycleTime
,
VendorID
and
DeviceID
settings only ap-
pear for the IOL Manual selection in the
Port mode (pin 4)
drop-down menu.
Changes to settings require operator or admin rights. If you do not have these, the
Con-
figuration
tab is grayed out, and the displayed values cannot be edited.
If cyclic data exchange takes place via PROFINET, no configuration is possible. In this
case, a message appears:
Note: Changing configuration not allowed because interface state
is “communicating.”
To makes changes to a port’s configuration, proceed as follows:
1. Select the desired port (port X01, port X02 etc.) from the menu
2. Open the
Configuration
tab.
3. Configure pin 4 by setting the port operating mode.