765-4501/0100-0000
Commissioning
Product manual | Version: 1.1.0
89
8PORT IOL-A FLD EI DC 24V 2.0A
Value
Port Status
Description
2
Incorrect Device
The version or compatibility check
failed
3
Preoperate
The product is ready for communi-
cation
4
Operate
The product is communicating
5
DI CQ
The port is in digital input mode
6
DO CQ
The port is in digital output mode
7
Reserved
Reserved
8
Reserved
Reserved
9
Incorrect Cycle Time
The cycle time according to the con-
figuration does not correspond to
the connected product
254
Port Power Off
The port voltage is switched off
255
Not Available
The port is not available
10.3.1.3.5 Quality
This shows the
Port Quality Info
, including information on the validity of the process data
for input and output (separately). The content is binary coded.
Table 56: Meaning of the Individual Bits
Bits of Port Quality Info
Description
Bit 0
0 = input process data valid
1 = input process data invalid
Bit 1
0 = output process data valid
1 = output process data invalid
Bit 2 to bit 7
Reserved