765-4501/0100-0000
Commissioning
Product manual | Version: 1.1.0
113
8PORT IOL-A FLD EI DC 24V 2.0A
Node Name
Node Class
Access
Description
Model
Variable
Read
Model name of the device: “IO System
Field-765-xxxx”
ProductCode
Variable
Read
Product code of the device: “765-xxxx/xxxx-
xxxx”
RevisionCounter
Variable
Read
Hardware version of the device
SerialNumber
Variable
Read
Serial number of the device
SoftwareRevision
Variable
Read
Revision/version of the device firmware
10.3.4.1.2 Configuring Parameters
The OPC UA server provides nodes with configuration parameters for the device. For ex-
ample, the OPC UA client can read out the upper limiting value for temperature in the
OverTemperature
node. The path to this node is:
Root > Object > DeviceSet > [device name] > IOLinkMaster > Diag-
nostics > Configuration
The following table lists device-specific configuration parameters.
Table 71: Device-Specific Configuration Parameters
Node Name
Node Class
Access Default Description
CurrentHysteresis
Variable
Read
10 mA
Current hysteresis; unit: mA
If the current exceeds the limiting value, the cur-
rent must fall back below the limiting value by the
hysteresis to revoke the diagnosis.
OverTemperature
Variable
Read
70 °C
Upper limiting value for the temperature of a port;
unit: 0.1 °C
OverVoltageL
Variable
Read
30 V
Upper limiting value for the voltage in supply ca-
ble 1; pins with the following functions can be
monitored: L+, DI, DO, DIO, IO-Link; unit: mV
OverVoltageL2
Variable
Read
30 V
Upper limiting value for the voltage in supply ca-
ble 2; unit: mV
TemperatureHysteresis
Variable
Read
2 °C
Temperature hysteresis; unit: 0.1 °C
If the temperature exceeds the limiting value, the
temperature must fall back below the limiting
value by the hysteresis to revoke the diagnosis.
UnderTemperature
Variable
Read
−25 °C Lower limiting value for the temperature of a port;
unit: 0.1 °C
UnderVoltageL
Variable
Read
18 V
Lower limiting value for the voltage in supply ca-
ble 1; pins with the following functions can be
monitored: L+, DI, DO, DIO, IO-Link; unit: mV
UnderVoltageL2
Variable
Read
18 V
Lower limiting value for the voltage in supply ca-
ble 2; unit: mV
VoltageHysteresis
Variable
Read
300 mV Voltage hysteresis; unit: mA
If the voltage exceeds the limiting value, the volt-
age must fall back below the limiting value by the
hysteresis to revoke the diagnosis.
The OPC UA server provides nodes with configuration parameters for each port. The
path to this node is:
Root > Object > DeviceSet > [device name] > IOLinkMaster > Diag-
nostics > PortXX > Configuration