765-4501/0100-0000
Commissioning
88
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
10.3.1.3.3 Displaying Port Status Information
Figure 14:
Port XX
Menu Item,
Status
Tab
The
Status
tab shows status information for pins 2 and 4 of the selected port.
This tab answers the following questions about the selected port:
• What is the current port status of the port?
• Is the process data valid for input/output?
• Is a product connected to the selected port? If so, what is this product’s version ID?
• How high is the data transmission rate between the port and a product connected
there?
• How long is the communication cycle time in the
Operate
operating mode?
• What is the true input/output data length of the connected product in bytes?
• What is the manufacturer ID or product ID of the product connected to the IO-Link
port?
Proceed as follows to display the status information on a specific port:
1. From the main menu of the Webserver (left), select the menu item which you want to
view information about.
2. Open the
Status
tab.
ð
The
Status
tab opens. The current port status information appears.
10.3.1.3.4 State
This shows the current port status information of the IO-Link port. The following table con-
tains all possible values for the status of the IO-Link port:
Table 55: Possible Values of “State” (Port Status Information)
Value
Port Status
Description
0
No Device
No product is connected to the port,
or there is no communication with
the connected product
1
Disabled
The port is inactive