298 Diagnostics
WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
The DIA LED indicates following diagnostics:
Table 209
: “DIA” Diagnostics LED
Status
Explanation
Remedy
Off
There are no
PROFINET
diagnostics.
---
Yellow
There are diagnostics
with severity level
“Maintenance
Required” or
“Maintenance
Demanded.”
Proceed according to the message in
the PROFINET IO Controller
engineering tool.
Red
There are diagnostics
with severity level
“Error.”
Proceed according to the message in
the PROFINET IO Controller
engineering tool.
A configuration error
was detected in the
PROFINET
target/actual value
check. The
e!
COCKPIT
device
configuration does
not match the
PROFINET IO
Controller
configuration (this is
indicated in the
PROFINET IO
Controller
engineering tool).
Perform a GSDML export in
e!
COCKPIT
and import the data into the PROFINET
IO Controller engineering tool.