50
Device Description
WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
3.8.11
Connection Type
Table 24: Technical Data
– Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm²
… 2.5 mm², AWG 28 … 14
Stripped lengths
8 mm
… 9 mm / 0.33 in
Table 25: Technical Data
– Power Jumper Contacts
Power jumper contacts
Spring contact, self-cleaning
Table 26: Technical Data
– Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
3.8.12
Climatic Environmental Conditions
Table 27: Technical Data
– Climatic Environmental Conditions
Surrounding air temperature, operation 0 °C
… 55 °C
Surrounding air temperature, storage
−25 °C … +85 °C
Relative humidity without condensation 5 %
… 95 % without condensation
Operating altitude
0
… 2000 m
Pollution degree
2
Overvoltage category
II
Protection type
IP20
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
25 ppm
H
2
S
10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used
in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation